Operating advanced function
FIELD SETTING MODE
Water Law & Room Thermostat : Code 20✴✴
| Ts | ① |
|
|
| Ts : Target Temp. |
#2021/2031 |
|
| Cooling WL | |||
| ② | Ta : Ambient Temp. | ||||
|
|
| ① |
| ||
#2022/2032 |
|
|
|
| ||
|
|
|
|
| ||
#2061/2071 |
|
|
| ② |
| |
|
|
|
|
| Shift Value | |
#2062/2072 |
|
|
|
| ||
Heating WL |
|
| ���������� | |||
Floor | FCU |
|
|
| ||
|
|
|
|
| ||
|
| #2011 | #2012 | #2051 | #2052 | Ta |
|
|
|
|
|
|
Field Setting Value
Main Menu & | Sub Menu Function | Description | Sub | Default | Min | Max | Step | Unit | |
Code | Code | ||||||||
|
|
|
|
|
|
| |||
Water Law | Outdoor Temp for Water Law | Point ➀ | ✴✴11 | 5 | 1 | ˚C | |||
Code 20✴✴ | (Heating) | Point ➁ | ✴✴12 | 15 | 10 | 20 | 1 | ˚C | |
Water Out Temp for WL1 Heating | Point ➀ | ✴✴21 | 40 | 40 | 55 | 1 | ˚C | ||
| |||||||||
| Point ➁ | ✴✴22 | 25 | 17 | 37 | 1 | ˚C | ||
| Water Out Temp for WL2 Heating | Point ➀ | ✴✴31 | 50 | 40 | 55 | 1 | ˚C | |
| Point ➁ | ✴✴32 | 35 | 17 | 37 | 1 | ˚C | ||
| Heating Water Law for Auto Mode | WL Type | ✴✴41 | 1(WL1) | 1 | 2(WL2) | - | - | |
| Outdoor Temp for Water Law | Point ➀ | ✴✴51 | 30 | 25 | 35 | 1 | ˚C | |
| (Cooling) | Point ➁ | ✴✴52 | 40 | 35 | 45 | 1 | ˚C | |
| Water Out Temp for WL1 Cooling | Point ➀ | ✴✴61 | 25 | 18 | 25 | 1 | ˚C | |
| Point ➁ | ✴✴62 | 18 | 5 | 18 | 1 | ˚C | ||
| Water Out Temp for WL2 Cooling | Point ➀ | ✴✴71 | 18 | 18 | 25 | 1 | ˚C | |
| Point ➁ | ✴✴72 | 5 | 5 | 18 | 1 | ˚C | ||
| Cooling Water Law for Auto Mode | WL Type | ✴✴81 | 1(WL1) | 1 | 2(WL2) | - | - | |
| External Thermostat Application | #1(Floor) | ✴✴91 | 0(No) | 0 | 1(Yes) | - | - | |
| #2(FCU) | ✴✴92 | 0(No) | 0 | 1(Yes) | - | - | ||
|
|
Water Law for Heating
•Outdoor air temperature range : Lower limit ➀(#2011, Default
-With this default settings, the water outlet temperature by heating water law can be changed within the outdoor temperature range of
•Water out temperature range for floor/FCU applications respectively :
Upper limit ➀(#2021/2031, Default 40/50˚C, Range : 40 ~ 55˚C), Lower limit ➁(#2022/2032,
Default 25/35˚C, Range : 17 ~ 37˚C)
-With this default settings, the water outlet temperature by heating water law can be changed within the range of 25/35 ~ 40/50˚C.
•Type of water law for according to heating devices(floor/FCU) : #2041(Default “1”(WL1 for floor)), “2”(WL2 for FCU or radiator)
•The #2 DIP switch in the wired remote controller should be set to “OFF”(Default) to control the water outlet temperature.
•The operation mode of the wired remote controller should be set to “AUTO”() to use the weather dependent water law scheme.
34_ Operating advanced function