TROUBLESHOOTING TIPS

If the unit has some problem to work properly, the LED on hydro unit will flash and some error codes will be displayed on the controller.

The following table described the explanation of error codes on the LCD display.

Thermistor

Check its resistance. 10kohm @ 24°C(Hydro unit), 220kohm@24°C(DHW Tank, Solar)

Check its location as shown at the diagram.

Check its contact status with pipe.

Final solution is to change parts.

Display

Explanation

EVA Inlet thermistor SHORT or OPEN

EVA Outlet thermistor SHORT or OPEN

Wired remote controller thermistor SHORT or OPEN

FRAM Read/Write Error(Wired remote controller data error)

Water Inlet thermistor SHORT or OPEN

Water Outlet thermistor SHORT or OPEN

PHE thermistor SHORT or OPEN

Water TANK thermistor SHORT or OPEN

ENGLISH

E903

 

 

 

PHE

 

 

 

thermistor

 

 

 

 

Water

 

 

 

outlet

 

 

Tw3

E902

Tw2

EVA inlet

 

 

 

 

 

Tr1

E122

 

 

 

Ref' In

 

 

Tr2

Ref' Out

 

 

EVA outlet

 

 

Tw1

E123

 

 

 

 

 

Water inlet

 

 

E901

 

Water Out

Water In

 

 

 

 

Wired remote controller thermistor

E653

Water tank thermistor E904

Appendix _45

Page 45
Image 45