ENVIRONMENTALLY FRIENDLY TECHNOLOGY
SUPER ABSORPTION
Sequence of cooling operation (DE)
Sequence of heating operation (DE)
Figure 27 illustrates the typical operating sequence of a SANYO DE di-
With a chilled water setpoint of 6.7° C and with the chiller/heaters en- abled, the start signal will be energized as the leaving chilled water tem- perature rises to 7.7° C, 1.0° C above setpoint.
The burner initially completes a
The No. 1 absorbent pump flow rate is changed during all stages of op- eration to insure quicker
Figure 27. Typical combustion time chart (cooling operation)
Start signal
As the cooling load is satisfied with the chiller/heaters at minimum load, the unit will cycle off as the leaving chilled water temperature drops to 5.5° C, 1.5° C below setpoint.
When the microprocessor issues a stop signal, the generator heat source will shut off and the dilution cycle will start. The dilution cycle will last between 6 and 15 minutes depending on generator temperature. The dilution cycle will consist of stopping of the refrigerant pump, absorbent pump(s), and the cooling water pump in turn. The unit is capable of re- starting during the dilution cycle.
Stop signal
Figure 28 illustrates the typical operating sequence of a SANYO DE di-
With a hot water setpoint of 55° C, the start signal will be energized as the leaving heating water temperature drops to 54° C, 1.0° C below setpoint. The burner initially completes a
Figure 28. Typical combustion time chart (heating operation)
Start signal
As the heating load is satisfied with the chiller/heaters at minimum load, the unit will cycle off as the leaving heating water temperature rises to 57° C, 2° C above setpoint.
When the microprocessor receives a stop signal, the generator heat source will shut off and the dilution cycle will begin. The dilution cycle will last approximately 5 minutes depending on generator temperature. The dilution cycle consists of timed stopping of the No. 1 absorbent pump. The chiller/heaters is capable of restarting during the dilution cycle.
Stop signal
Chiller stop
| 4 | 2 | 8 | 2 | Control | ||
| 36 sec. | sec. | sec. | sec. | sec. | area | 12 sec. |
Burner | ON |
|
|
|
|
|
|
Blower | OFF |
|
|
|
|
|
|
Gas control | Open |
|
|
|
|
|
|
valve | Close |
|
|
|
|
|
|
Ignition | ON |
|
|
|
|
|
|
| OFF |
|
|
|
|
|
|
Sol. valve | ON |
|
|
|
|
|
|
Ignition gas | OFF |
|
|
|
|
|
|
Sol. valve | ON |
|
|
|
|
|
|
Main gas | OFF |
|
|
|
|
|
|
No. 1 ABSO | ON |
|
|
|
|
|
|
pump | OFF |
|
|
|
|
|
|
No. 2 ABSO | ON |
|
|
|
|
|
|
pump | OFF |
|
|
|
|
|
|
Refrigerant | ON |
|
|
|
|
|
|
pump | OFF |
|
|
|
|
|
|
Approx. 5 min. | Dilution cycle |
Approx. 6
Chiller stop
| 4 | 2 | 8 | 2 | Control | ||
| 36 sec. | sec. | sec. | sec. | sec. | area | 12 sec. |
Burner | ON |
|
|
|
|
|
|
Blower | OFF |
|
|
|
|
|
|
Gas control | Open |
|
|
|
|
|
|
valve | Close |
|
|
|
|
|
|
Ignition | ON |
|
|
|
|
|
|
| OFF |
|
|
|
|
|
|
Sol. valve | ON |
|
|
|
|
|
|
Ignition gas | OFF |
|
|
|
|
|
|
Sol. valve | ON |
|
|
|
|
|
|
Main gas | OFF |
|
|
|
|
|
|
No. 1 ABSO | ON |
|
|
|
|
|
|
pump | OFF |
|
|
|
|
|
|
| Approx. 5 min. |
| Dilution cycle |
|
|
| Approx. 5 min. |
36 | 37 |