Sanyo DE Installation and application data, Location and space requirements, Water piping, water

Models: DE

1 50
Download 50 pages 27.2 Kb
Page 46
Image 46
Installation and application data

ENVIRONMENTALLY FRIENDLY TECHNOLOGY

 

200

 

53 52 51

 

42

 

41

32

 

 

31

24

100

23

90

 

80

 

70

 

60

 

 

SUPER ABSORPTION

 

 

 

 

 

 

 

 

 

Installation and application data

 

 

 

 

 

 

 

Location and space requirements

 

 

 

The unit is designed for indoor application and must be located in a space

provided on either end to facilitate tube cleaning, or removal and clear-

 

where the surrounding temperature of equipment is between 5° C and

ance on all other sides of the unit for general unit maintenance. See the

 

45° C, and at no more than 90% relative humidity. Clearance must be

dimensional data tables for clearance requirements.

 

Water piping

 

 

 

Water piping should be arranged so that the circulating pumps discharge

and noise transmission, vibration absorbers should be provided. Shutoff

 

directly into the vessels. The water piping should be insulated to reduce

valves should be provided to allow unit isolation during maintenance.

 

heat gain and to prevent condensation. Air vents should be located at all

Chilled water flow switch is provided on the unit and is preset to open at

 

high points in the water piping system, and drains should be located at all

approximately 50% of specified flow rate.

 

low points to facilitate complete system drainage. To reduce vibration

 

 

22

50

 

21

 

40

14

12

13

11

 

30

 

/h)

 

3

 

(m

Field piping instruction

1.In order to prevent freeze-up of chilled water during unit shutdown, the chilled water pump(s) and air handler must be run for 15 minutes after the burner is shut off. This will allow time for the automatic dilu- tion cycle to be completed.

2.The standard unit must not be subjected to water pressures in excess of 981 kPa (10 kg/cm2G).

3.An expansion tank should be provided in the chilled/hot water line.

4.Thermometers and pressure gauges should be field-installed at the inlet and outlet of the chilled/hot water line, and the cooling water

line.

5.During heating operation, the cooling water circuit should not be in operation and should be blown down.

6.All external piping connections are provided with JIS 10K flanges un- less noted.

7.A drain line must be installed from the smoke chamber drain to a floor drain.

8.See Figure 32 (DE), Figure 48 (NE), Figure 61 (LE) for typical sys- tem piping arrangement.

03

20

Flowrate

(LE)

 

 

 

 

02

 

 

 

10

dropcurve

 

 

 

 

01

 

 

 

8 9

pressure

 

 

 

 

 

 

 

 

6 7

water

 

 

 

 

 

 

 

 

5

Hot

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4

Graph17.

 

 

 

 

 

 

 

 

3

100

90

80

70

60

50

40

30

20

10

 

 

 

 

 

 

(kPa) drop Pressure

 

 

Leveling requirements

Strict leveling tolerances must be adhered to for trouble-free operation.

difference in the water level at the two points. The tolerance that must be

SANYO units are furnished with four leveling reference points, one on

maintained from end-to-end and side-to side is 1mm (1/25'') of difference

each corner of the lower shell or tube sheet. Each reference point is

for each 1m length between points. It is not necessary to check levels

designated by three punch marks. A convenient method to check level-

diagonally. When the unit does not meet this requirement, the unit must

ing tolerances is to fill a clear vinyl hose with water and measure the

be shimmed in order to meet leveling tolerances.

Figure 62. Leveling the chiller

 

B

D

Evaporator side

A

Absorber side

C

88

89

Page 46
Image 46
Sanyo DE Installation and application data, Location and space requirements, Water piping, Field piping instruction, water