ENVIRONMENTALLY FRIENDLY TECHNOLOGY
SUPER ABSORPTION
SANYO control system
The SANYO control system surpasses other proportional only control systems available today. The digital PID(proportional, integral, and dif- ferential) control maximizes unit performance by maintaining a ± 0.5° C deviation in leaving chilled water temperature from setpoint. Proportional controls typically can only maintain a ± 1° C deviation from setpoint. The controller's innovative design also incorporates the ability to start and stop the system chilled/hot and cooling water pumps. During shutdown these pumps are sequenced to insure a complete dilution cycle.
The leaving chilled water temperature is measured every five seconds and fuel input is changed according to the gradient of the leaving chilled water temperature curve. System temperatures, setpoints, and opera-
tional records are displayed along with indicator lights for the chiller, pumps and burner.
The SANYO control system offers its users
Display and control board
Table 2. Typical operation data
Temperature | High temperature generator |
| Exhaust gas |
| Chilled water |
| Cooling water |
| Hot water |
Operation hours | Chiller / heater |
| Combustion |
| No.1 Absorbent pump |
| Refrigerant pump |
Message | Low level vacuum (Notice / Caution) |
Display and control board
■Display(normal)
| High concentration (Notice / Caution) |
| Foul tube of cooling water (Notice / Caution) |
| High cooling water temperature (Notice / Caution) |
| Foul chamber (Notice / Caution) (only for |
Set point | Chilled water |
| Hot water |
|
|
Chiller / heater | |
| Burner |
H Generator temp 149 . 9 ° C
Table 1. | Indication lamp |
|
|
|
|
symbol | Name | Lamp color |
| Running(Operation) indication lamp | Red |
| Stop indication lamp | Green |
| Alarm indication lamp | Orange |
| Bunner combustion indication lamp | Red |
| Cooling / Heating indication lamp | Orange |
| Remote / Local select button with lamp | Red |
| Mode select button with lamp | Red |
| Data display | LCD |
|
|
|
SETTING | STOP RUN | COOLING | BURNER |
| CHILLER | HEATING | ALARM |
| REF PUMP | BUZZER STOP | |
| #1 ABS PUMP | MODE |
|
|
|
| |
| #2 ABS PUMP | OPERATION | REMOTE |
| PURGE PUMP |
|
|
| BURNER BLOWER | STOP | LOCAL |
Sample 1. |
|
Exhaust gas temp | 236° C |
CH W temp | 12.3 7.1° C |
Sample 2.
Notice : Low level vacuum
Caution : Foul tube of COW
Table 3. Typical alarm data
Operation alarm | Generator solution level |
| Thermal relay of No.1 Absorbent pump |
| Thermal relay of No.2 Absorbent pump |
| Thermal relay of burner blower |
| Thermal relay of oil pump |
| Thermal relay of refrigerant pump |
| Interlock of chilled water pump |
| Interlock of hot water pump |
| Interlock of cooling water pump |
| Interlock of system |
| Generator pressure |
| Chilled water flow rate |
| Hot water flow rate |
| Generator temperature |
| High concentration |
| Purge tank pressure sensor |
| Solution temp sensor |
Others | Condensed refrigerant temp sensor |
| Generator temp sensor |
| Chilled water sensor |
| Hot water sensor |
| Cooling water sensor |
| Refrigerant temp sensor |
| Power failure |
|
|
6 | 7 |