Sanyo DE Foundation dimensional data NE, Control panel NE, H Generator temp 149 . 9 C, Name

Models: DE

1 50
Download 50 pages 27.2 Kb
Page 31
Image 31
Foundation dimensional data (NE)

ENVIRONMENTALLY FRIENDLY TECHNOLOGY

Foundation dimensional data (NE)

Figure 44. NE-11 Thru NE-42

 

 

 

A

 

F

 

 

 

 

AA

BB

 

 

 

G

E

 

K

C

J

D

Figure 45. NE-51 Thru NE-82

A

BB

F

AA

BB

G

E

C

J

D

K

SUPER ABSORPTION

Control panel (NE)

 

SETTING STOP RUN

 

H Generator temp 149 . 9 ° C

CHILLER

ALARM

REF PUMP

BUZZER STOP

 

 

#1 ABS PUMP

 

 

MODE

 

 

#2 ABS PUMP OPERATION

REMOTE

 

PURGE PUMP

 

 

STOP

LOCAL

150

NOTES :

150

Table 11. Indication lamp

symbol

Name

Lamp color

 

Running(Operation) indication lamp

Red

 

Stop indication lamp

Green

 

Alarm indication lamp

Orange

 

Remote / Local select button with lamp

Red

 

Mode select button with lamp

Red

 

Data display

LED

 

 

 

1.

The base of machine has ø 50 hole for anchor bolt.

5.

Surface of foundation should be made flat.

2.

Anchor bolt should be fixed by shown detail drawing.

6.

Anchor bolts and nuts are supplied by customer.

 

Washer should be welded with base.(Refer to Figure 21 page32)

 

 

3.There should be a drain ditch around the foundation.

4.The floor surface should be made as water proof for ease of maintenance work.

Table 10.

Dimensional data

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Model

 

 

Weight (kg)

 

 

 

 

 

Dimensions (mm)

 

 

 

 

No.

 

Oper.

AA

BB

A

B

C

D

E

F

G

J

K

NE-11

4,200

2,100

2,100

1,896

175

350

900

150

1,200

150

1,000

NE-12

4,400

2,200

2,200

1,896

175

350

900

150

1,200

150

1,000

NE-13

5,500

2,700

2,750

2,916

175

350

900

150

1,200

150

1,000

NE-14

5,700

2,850

2,850

2,916

175

350

900

150

1,200

150

1,000

NE-21

6,800

3,400

3,400

2,916

175

350

1,100

150

1,400

150

1,200

NE-22

7,100

3,550

3,550

2,916

175

350

1,100

150

1,400

150

1,200

NE-23

8,400

4,200

4,200

3,939

175

350

1,100

150

1,400

150

1,200

NE-24

8,800

4,400

4,400

3,939

175

350

1,100

150

1,400

150

1,200

NE-31

10,800

5,400

5,400

3,886

200

400

1,200

150

1,500

200

1,300

NE-32

11,200

5,600

5,600

3,886

200

400

1,200

150

1,500

200

1,300

NE-41

13,200

6,600

6,600

3,886

200

400

1,250

150

1,550

200

1,350

NE-42

13,600

6,800

6,800

3,886

200

400

1,250

150

1,550

200

1,350

NE-51

18,800

9,400

9,400

3,966

130

190

510

1,700

180

2,060

250

1,800

NE-52

20,400

10,200

10,200

4,508

130

190

510

1,700

180

2,060

250

1,800

NE-53

21,900

10,950

10,950

5,006

130

190

510

1,700

180

2,060

250

1,800

Figure 46. Control panel

1200

300

700

NE-61

26,600

13,300

13,300

4,466

140

210

560

1,800

180

2,160

300

1,900

NE-62

28,500

14,250

14,250

4,966

140

210

560

1,800

180

2,160

300

1,900

NE-63

30,500

15,250

15,250

5,491

140

210

560

1,800

180

2,160

300

1,900

NE-71

36,200

18,100

18,100

4,566

140

210

560

2,200

180

2,560

300

2,300

 

 

 

 

 

 

 

 

 

 

 

 

 

NE-72

38,200

19,100

19,100

5,091

140

210

560

2,200

180

2,560

300

2,300

 

 

 

 

 

 

 

 

 

 

 

 

 

NE-73

40,500

20,250

20,250

5,591

140

210

560

2,200

180

2,560

300

2,300

NE-81

43,600

21,800

21,800

5,091

140

210

560

2,400

180

2,760

300

2,500

 

 

 

 

 

 

 

 

 

 

 

 

 

NE-82

46,100

23,050

23,050

5,591

140

210

560

2,400

180

2,760

300

2,500

100

70 70

Steam control valve NE-11 thru NE-53 : ø 21 NE-61 thru NE-82 : ø 27

Power supply

NE-11 thru NE-53 : ø 33

NE-61 thru NE-82 : ø 41

70

Steam shutoff valve ø 21

Remote control ø 27

58

59

Page 31
Image 31
Sanyo DE Foundation dimensional data NE, Control panel NE, H Generator temp 149 . 9 C, Environmentally Friendly Technology