Configuration Extensions
104 372 SPU 780 01EMAN May 2002
Compact Phase II
Overview Compact Phase II extensions allow the programming of functions specific to the
Compact Phase II controllers. This provides support for:
PLC based password access
Secure Data Area (SDA)
Comm 1 CTS/RTS delay time settings.
Editing the
Compact Phase II
Extension
In the Active Extensions panel select the Compact Phase II extension, then:
Note: If the Compact Phase II extension does not appear in the Active Extensions
panel, it is not a valid extension for the current controller type.
Step Action
1 Enter a Secure Data Area value between 0 and 128 in the SDA Size (K Words)
box. A zero value disables the feature.
2 Enter a value between 0 and 50 in the CTS Delay (x10 ms) box. A zero value
indicates the feature is disabled.
Note: This value is a factor of 10; if 5 is entered, 50 is assumed by the PLC.
3 Enter a value between 0 and 50 in the RTS Delay (x10 ms) box. A zero value
indicates the feature is disabled.
Note: This value is a factor of 10; if 5 is entered, 50 is assumed by the PLC.
4 Enter a password consisting of a maximum of 16 characters (A-Z, 0-9 and _) in
the PLC Password boxes. The PLC password can only be changed while
online. If the password is set to nothing, the PLC is not password protected.