Troubleshooting
294 372 SPU 780 01EMAN May 2002
S901 Controller The I/O Module Health Status information consists of words that represent the
module health for channel pairs. Each word represents 2 channels. The words are
also divided into input modules and output modules. A single bit is used to repres ent
the Health Status of a single module.
If the slot is inhibited in the Traffic Cop then the bit will be a 0. If the slot contains
an input module then the bit will be a 1. This will not be the case if the
Communication Status Word 2/2 (183) indicates an error.
If the slot contains an output module and if the active light is on then this bit will be
a 1. If the active light is off then this bit will be a 0. It is common to set the status
indicator for an output slot to toggle between 0 and 1 when active and healthy.
The Upper byte contains the status of the lower channel number of the channe l pair
(for example, channel 1 for channel pair 1/2). The lower byte contains the status of
the higher channel number of the channel pair. Each byte represents the status of
slots 1 to 8 of the channel. The Most Significant Bit of the channel represents slot 1
and the Least Significant Bit shows the status of slot 8.
Status Word #012: Drop # 01/01 Rack # 1/5
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
Plus these five w/QuantumSlot #1 through Slot #11 E-Series