Schneider Electric ION8800 Mount the Meter, Order Options D/E Essailec Connector Arrangement

Models: ION8800

1 36
Download 36 pages 26.15 Kb
Page 13
Image 13
Order Options D/E Essailec Connector Arrangement

Order Options D/E Essailec Connector Arrangement

 

Meter Port

Essailec Connector Pin

Description

 

 

 

 

 

I11

A01

standard

 

 

 

 

 

I12

A1

standard

 

 

 

 

 

I21

A02

standard

 

 

 

 

Current

I22

A2

standard

Measurement Inputs

I31

A03

standard

 

 

 

 

 

I32

A3

standard

 

 

 

 

 

I41

A04

optional

 

 

 

 

 

I42

A4

optional

 

 

 

 

 

Uref

B0

standard

 

 

 

 

Voltage

U1

B1

standard

Measurement Inputs

U2

B2

standard

 

 

 

 

 

U3

B3

standard

 

 

 

 

 

DI-SCOM

B5

standard; Common

 

 

 

 

Digital Inputs

DI1

B6

standard

 

 

 

DI2

B7

standard

 

 

 

 

 

 

DI3

B8

standard

 

 

 

 

Power Supply Inputs

Power Supply N/-

B4

Power Supply neutral (-)

(AC/DC)

Power Supply L/+

B9

Power Supply line (+)

 

 

 

 

 

DO1 & DO2 K

C0

standard; Common

 

 

 

 

 

DO1

C1

standard; NO

 

 

 

 

 

DO1

C2

standard; NC

 

 

 

 

 

DO2

C3

standard; NO

 

 

 

 

Form C Solid-state

DO2

C4

standard; NC

Relays

DO3 & DO4 K

C5

standard; Common

 

 

 

 

 

DO3

C6

standard; NO

 

 

 

 

 

DO3

C7

standard; NC

 

 

 

 

 

DO4

C8

standard; NO

 

 

 

 

 

DO4

C9

standard; NC

 

 

 

 

 

Alarm K

D0

standard; Common

 

 

 

 

Form C Mechanical

Alarm

D1

standard; NO

Relay

Alarm

D2

standard; NC

 

 

 

 

 

-

D3

Unused

 

 

 

 

 

RS-485 Shield

D5

RS-485 Shield

 

 

 

 

RS-485 Com

RS-485 +

D6

RS-485 +

 

 

 

RS-485 -

D7

RS-485 -

 

 

 

 

 

 

-

D8

Unused

 

 

 

 

IRIG-B Clock

IRIG-B input common

D4

optional; clock synch input

Synchronization

Common

 

 

Input

 

 

 

IRIG-B input

D9

optional; clock synch input

 

 

 

 

Step 1: Mount the Meter

Meter Battery Considerations

The meter’s battery life expectancy depends on both temperature and the amount of time the meter is without power. For typical installations, the battery should last 10 years minimum at 25ºC meter ambient operating temperature. The battery is field replaceable (see “Replacing the Battery” on page 31).

© 2007 Schneider Electric. All rights reserved.

13

Page 13
Image 13
Schneider Electric ION8800 Mount the Meter, Order Options D/E Essailec Connector Arrangement, Meter Battery Considerations