Schneider Electric ION8800 manual Ethernet Connections optional module, 10Base-T, 10Base-FL Fiber

Models: ION8800

1 36
Download 36 pages 26.15 Kb
Page 21
Image 21
Ethernet Connections (optional module)

Ethernet Connections (optional module)

10Base-T

Pin 1: Transmit Data +

Pin 2: Transmit Data -

Pin 3: Receive Data -

Pin 6: Receive Data +

Wire Type

High quality Category 3 or 5 unshielded twisted pair cable

Connector Type

RJ45 modular

Maximum Length

100 m (328 ft)

Type

IEEE 802.3 10Base-T for 10 Mbps base band CSMA/CD LANs

Data Rate

10 Mbps

Isolation

Transformer isolated to 1500 VAC/2250 VDC RMS

Max. Connections Allowed

4 simultaneous

10Base-FL (Fiber)

Wire Type

62.5/125 micrometer multimode fiber optic cable

Connector Type

ST

Maximum Length

2000 m (6562 ft)

Data Rate

10 Mbps

Isolation

Optical

10Base-T NOTE

ST type fiber cables Ethernet connection should be made to either the Fiber port or RJ45 port, not both, or communications conflicts may result.

Only one EtherGate connection per port is allowed at a time

Ethernet TCP/IP Service Ports

Protocol

Port

ION

7700

 

 

Modbus RTU

7701

Modbus TCP

502

 

 

EtherGate (COM2)

7802

 

 

EtherGate (COM3)

7803

DNP TCP

20,000

 

 

Internal Modem Connection (COM4 optional module)

 

 

 

 

 

 

Pin 3: Ring

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Pin 4: Tip

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Connector Type

RJ11

Wire Type

Part 68 compliant telephone cord

 

 

Data Rate

300 bps – 56 kbps

 

 

Error Correction

V.42 LAPM, MNP 2-4, V.44

Data Compression

V.42 bis/MNP 5

 

 

 

 

 

 

 

© 2007 Schneider Electric. All rights reserved.

21

Page 21
Image 21
Schneider Electric ION8800 Ethernet Connections optional module, Internal Modem Connection COM4 optional module, 10Base-T