Schneider Electric ION8800 Replacing the Battery, Battery Specifications, Battery Dimensions

Models: ION8800

1 36
Download 36 pages 26.15 Kb
Page 31
Image 31
Replacing the Battery

Replacing the Battery

The battery in the ION8800 meter keeps the real time clock running when supply power is lost. Replace the battery if the meter has been stored for an extended period of time without power (longer than two years). If the meter will be without power for an extended length of time, disconnect the battery cable so that the battery maintains its 10-year shelf life.

Battery Specifications

Type

Lithium LiSOCl2

Nominal Capacity

1.0

Ah

 

 

 

Rated Voltage

3.6

V

Connector

Gold-plated

 

 

 

Battery Dimensions

Gold-plated

Connector

The battery can be changed when the meter is either powered or unpowered.

Battery Specifications NOTE

Replacing the battery on an unpowered meter resets the internal clock and may affect revenue parameters.

To replace the battery

1.To prevent electrostatic damage to the unit, make sure you are grounded or wear an anti-static wrist strap during this procedure.

2.Open the front cover of the meter.

3.Remove the Phillips screw that holds the battery cover in place and remove the battery cover.

4.Remove the battery from the housing and disconnect the battery connector from the meter.

Battery

Connector

Battery Cover Battery Dimensions

Battery

5.Connect the new battery’s wire to the meter. and place the battery in the housing.

6.Replace the battery cover and the Phillips screw.

7.Close the cover of the meter.

© 2007 Schneider Electric. All rights reserved.

31

Page 31
Image 31
Schneider Electric ION8800 manual Replacing the Battery, Battery Specifications, Battery Dimensions, To replace the battery