Step 4: Wire the Communications

Step 4: Wire the Communications

ION8800 meters are equipped with one standard optical port. Other communications ports are available as options.

The Communications module cover plate (found on the back of the meter) should never be removed unless a communications module is installed in its place.

Infrared Connections (COM1)

Connect an optical probe cable (not included) to communicate between the meter optical port and a PC serial port.

Interface

IEC 1107 optical port

Location

Front of meter

Data Rate

1,200 – 19,200 bps

Isolation

Optical

Duplex

Half

RS-485 Connections (COM2 and COM3)

Ports Available

COM2: optional module or Essailec

COM3: optional module only

 

 

 

Connectors

Captured-wire (+, –, Common*, Shield)

Wire

Shielded 2 or 3-conductor RS-485 cable

 

 

Maximum Cable Length

1219 m (4,000 ft) total for entire bus

 

 

Data Rate

300 – 57,600 bps

Maximum Devices (per bus)

32

 

 

Isolation

Optical

 

 

Duplex

Half

* Use optional Common wire for improved communications performance.

RS-232 Connections (COM3 optional module)

5

1

9

6

DB9 Null Modem

Wiring Diagram

DTE

DTE

(computer)

(meter)

Null modem cable pinout Pin 3 - Transmit Data - Pin 2 Pin 2 - Receive Data - Pin 3 Pin 7 - Request to Send- Pin 8 Pin 8 - Clear to Send- Pin 7 Pin 5 - Signal Ground- Pin 5 Pin 6 - Data Set Ready- Pin 4 Pin 4 - Data Terminal Ready- Pin 6

Specification

Meter Connected to Computer

Meter Connected to External

Modem

 

 

 

 

 

Connector Type

DB9 female end for mating with

male connector on the meter

 

 

 

Wire

Null modem RS-232 cable

Straight-through RS-232 cable

 

 

 

Maximum Cable Length

15.2 m (50 ft)

 

 

 

 

Data Rate

300 – 115,200 bps

 

 

 

 

Isolation

Optical

 

 

 

 

Duplex

Full

 

 

 

 

20

© 2007 Schneider Electric. All rights reserved.