Step 4: Wire the Communications
ION8800 meters are equipped with one standard optical port. Other communications ports are available as options.
The Communications module cover plate (found on the back of the meter) should never be removed unless a communications module is installed in its place.
Infrared Connections (COM1)
Connect an optical probe cable (not included) to communicate between the meter optical port and a PC serial port.
Interface | IEC 1107 optical port |
Location | Front of meter |
Data Rate | 1,200 – 19,200 bps |
Isolation | Optical |
Duplex | Half |
RS-485 Connections (COM2 and COM3)
Ports Available | COM2: optional module or Essailec | |
COM3: optional module only | ||
| ||
|
| |
Connectors | ||
Wire | Shielded 2 or | |
|
| |
Maximum Cable Length | 1219 m (4,000 ft) total for entire bus | |
|
| |
Data Rate | 300 – 57,600 bps | |
Maximum Devices (per bus) | 32 | |
|
| |
Isolation | Optical | |
|
| |
Duplex | Half |
* Use optional Common wire for improved communications performance.
RS-232 Connections (COM3 optional module)
5 | 1 |
9 | 6 |
DB9 Null Modem
Wiring Diagram
DTE | DTE |
(computer) | (meter) |
Null modem cable pinout Pin 3 - Transmit Data - Pin 2 Pin 2 - Receive Data - Pin 3 Pin 7 - Request to Send- Pin 8 Pin 8 - Clear to Send- Pin 7 Pin 5 - Signal Ground- Pin 5 Pin 6 - Data Set Ready- Pin 4 Pin 4 - Data Terminal Ready- Pin 6
Specification | Meter Connected to Computer | Meter Connected to External | |
Modem | |||
|
| ||
|
|
| |
Connector Type | DB9 female end for mating with | male connector on the meter | |
|
|
| |
Wire | Null modem | ||
|
|
| |
Maximum Cable Length | 15.2 m (50 ft) |
| |
|
|
| |
Data Rate | 300 – 115,200 bps |
| |
|
|
| |
Isolation | Optical |
| |
|
|
| |
Duplex | Full |
| |
|
|
|