The following table lists all settings that can be configured via the front panel, with the meter cover seal in place.
Menu
Setting
Description
Range (Values)
Default
|
|
|
| ||
|
| The power system’s configuration – | DELTA |
| |
| Volts Mode | ||||
| WYE, DELTA, etc. | ||||
|
| SINGLE |
| ||
|
|
|
| ||
|
|
| DEMO |
| |
|
|
|
|
| |
| PT Primary | The Potential Transformer’s primary | 1 to 999 999 999 | 120,00 | |
| winding voltage rating | ||||
|
|
|
| ||
|
|
|
|
| |
| PT Secondary | The Potential Transformer’s | 1 to 999 999 999 | 120,00 | |
| secondary winding voltage rating | ||||
|
|
|
| ||
|
|
|
|
| |
| CT Primary | The Current Transformer’s primary | 1 to 999 999 999 | 5 | |
| winding current rating | ||||
|
|
|
| ||
|
|
|
|
| |
| CT Secondary | The Current Transformer’s | 1 to 999 999 999 | 5 | |
| secondary winding current rating | ||||
|
|
|
| ||
|
|
|
|
| |
| I4 Primary | Primary rating for the I4 current | 1,0 - 999 999,00 | 5 | |
Setup | transformer | ||||
|
|
| |||
|
|
|
| ||
I4 Secondary | Secondary rating for the I4 current | 1,0 - 999 999,00 | 5 | ||
|
|
|
| ||
Basic |
| transformer |
|
| |
|
|
|
| ||
U1 Polarity | The polarity of the Potential | Normal or Inverted | Normal | ||
| |||||
| Transformer on U1 | ||||
|
|
|
| ||
|
|
|
|
| |
| U2 Polarity | The polarity of the Potential | Normal or Inverted | Normal | |
| Transformer on U2 | ||||
|
|
|
| ||
|
|
|
|
| |
| U3 Polarity | The polarity of the Potential | Normal or Inverted | Normal | |
| Transformer on U3 | ||||
|
|
|
| ||
|
|
|
|
| |
| I1 Polarity | The polarity of the Current | Normal or Inverted | Normal | |
| Transformer on I1 | ||||
|
|
|
| ||
|
|
|
|
| |
| I2 Polarity | The polarity of the Current | Normal or Inverted | Normal | |
| Transformer on I2 | ||||
|
|
|
| ||
|
|
|
|
| |
| I3 Polarity | The polarity of the Current | Normal or Inverted | Normal | |
| Transformer on I3 | ||||
|
|
|
| ||
|
|
|
|
| |
| I4 Polarity | The polarity of the Current | Normal or Inverted | Normal | |
| Transformer on I4 | ||||
|
|
|
| ||
|
|
|
|
| |
| Phase Rotation | Power system’s phase rotation | 123, 132 | 123 | |
|
|
|
|
| |
Demand | SWD Subinterval | Intervals used to compute your | 1 to 5 940 | 600 | |
Sliding Window Demand values | |||||
|
|
| |||
|
|
|
| ||
SWD # | The number of SWD periods in use | 1 to 15 | 3 | ||
| |||||
| Subintervals | ||||
|
|
|
| ||
|
|
|
|
| |
| SWD Pred Resp |
| 0,00 to 99,00 | 70 | |
|
|
|
|
| |
| Protocol | Specifies which protocol is active | ION, Modbus RTU, DNP, | ION | |
| DLMS, Factory | ||||
|
|
|
| ||
|
|
|
|
| |
| Baud Rate | Specifies COM port baud rate | 1 200 to 19 200 | 9 600 | |
COM1 | during serial communications | ||||
|
|
| |||
|
|
|
| ||
Transmit Delay | Specifies the meter’s transmit delay | 0 to 1,0 | 0,010 | ||
| setting (in seconds) | ||||
|
|
|
| ||
|
|
|
|
| |
| Unit ID | Identifies the meter during serial | 1 to 9 999 | From serial | |
| communications | number2 | |||
|
|
| |||
| Serial Port | Parity and stop bits for the port | 8N1,8N2,8E1,8E2,8O1,8O2 | 8N1 | |
|
|
|
|
|
© 2007 Schneider Electric. All rights reserved. | 23 |