4-Wire Wye, 3-Element, Direct Connection Diagram

4-Wire Wye, 3-Element, Direct Connection Diagram

LINE

LOAD

288V L-N / 500 V L-L max. VOLTS MODE = 4W-Wye

4-Wire Wye, 3-Element, 3 PTs Connection Diagram

LINE

LOAD

Use PTs for voltages over 288 V L-N / 500 V L-L.

Wye (Star) wiring for PT primaries and secondaries.

VOLTS MODE = 4W-Wye

4-Wire Wye, 2½-Element, 2 PTs Connection

LINE

LOAD

Phase 2 voltage (U2) displayed by meter is derived from phase 1 and phase 3, not measured. U2 will display a value even if no voltage is present on Phase 2. U2 values are only accurate for balanced loads. VOLTS MODE = 3W-Wye