Schneider Electric ION8800 manual Environmental Specifications IEC62052-11, Installation DANGER

Models: ION8800

1 36
Download 36 pages 26.15 Kb
Page 14
Image 14
Environmental Specifications (IEC62052-11)

Meter Ground

Terminal

ION8800

Meter

Slot-head

Screws

Environmental Specifications (IEC62052-11)

Mounting Location

Indoor use

Metrological

-10 to +45ºC (14 to +113ºF)

 

 

Operating Range

-25 to +55ºC (-13 to +131ºF)

No formation of ice

 

 

 

Max. Altitude

2000 metres (6562 feet) above sea level

 

 

Display Operating Range

-10 to +60ºC (14 to +140ºF)

Storage Range

-25 to +70ºC (-13 to +158ºF)

 

 

Relative Humidity Range

5 to 95% non-condensing

 

 

Enclosure Rating

IP51 (IEC60529)

Installation

Installation DANGER

Do not power up the meter until the ground terminal is connected -- risk of electric shock.

1.Connect the ground terminal on the rear of the meter to a good earth ground on the rack, using a 3.3 mm2 (12 AWG) wire. Ensure that the terminal nut is tightened down securely onto the ground wire. The wire must be a minimum of 30 cm long (11.8”) to allow racking and unracking.

2.Slide the meter into the DIN standard 43862 rack (half-width 19 inch/ 482.6 mm rack with plug-in Essailec connector).

9.37mm .49”)(1

465 mm (18.31”)

(0.28”)

 

 

451 mm (17.76”)

7 mm

133mm 24”).(5

.571 mm 25”).(2

Cut-out for 482.6 mm (19”)

Chassis

 

 

M6

3.Ensure the rear connector fits tightly.

4.Tighten the 2 slot-head screws (M3 thread) into the front of the meter rack, to hold the meter firmly in place.

Meter Essailec

Rack Essailec

Connector

Connector

 

482.6 mm (19”) Rack

14

© 2007 Schneider Electric. All rights reserved.

Page 14