9.2200/400 Voltage Changeover - Dual Voltage System

9.2200/400 Voltage Changeover - Dual Voltage System

The generator is incorporated with dual voltage system.

So, you can easily change 400/440V to 200/220V or adversely.

You can get 200V or 400V by changing the combination of output terminals with bus plates

①②

Danger

:Electrical Shock

￿Be sure to set the circuit breaker OFF and stop operation before setting.

Caution

:Damages to the property

￿Be sure to set the bus plates at the right positions and screw them securely.

￿Always ensure that the bus plate combination is correct (200V or 400V), connections of cables to the output terminals are correct and the voltage of loads is correct to use.

Turn off the both 3-Phase and 1-Phase breakers to OFF.

Open the box cover next to the control box and change the 6 bus plates connected to the output terminals to the required voltage combination.

WARNING LABEL (PART No.19402-00291)

(The left side toward the control panel)

BOX COVER

(Terminals and Bus plates are inside this cover)