Shindaiwa DG1000MI Initialization and pre-check, The earth leakage breaker relay has activated

Models: DG1000MI

1 52
Download 52 pages 13.75 Kb
Page 25
Image 25
7.3.3The earth leakage breaker relay has activated

7.3.3The earth leakage breaker relay has activated

In the event the earth leakage breaker relay has activated, the earth leakage indicating lamp Turns ON and the 3-Phase earth leakage breaker (lever) trips off to be positioned in the middle

between ON and OFF positions.

In the above condition, even though you stop the engine once and start it again, the 3-Phase Circuit breaker (lever) does not restore to ON or OFF, and the reset button does not function,

because the device keeps detecting current leakage.

Stop the engine promptly and find the leakage point to repair. After repairing the leakage point(s), proceed with the following restoration steps. (In the case the earth leakage indicating

lamp does not turn to ON simultaneously, the cause is Over-Loaded or Short-Circuit.)

Push the reset button or stop the engine.

Restore (Push-down) the 3-Phase circuit breaker (lever) and the 1-Phase circuit

breaker (lever) to OFF position.

By the above procedure, you can reset the breakers to ON positions.

8Initialization and pre-check

Danger

:Electrical Shock ￿ Injuries

￿Before performing any equipment check or maintenance, stop the engine, and remove the engine key. A person performing the maintenance should always keep the key.

Caution

:Fire ￿ Burns

￿When checking engine, always stop the engine, and keep away from fire. Wait until the engine cools down, before performing any checks.

Caution

:Fire

￿Always wipe any drip of fuel or oil. Do not use this equipment when a leak is found. Repair the equipment before use.

-25 -