:Electrical Shock ￿ Injuries
Adjust to the required voltage by adjusting Voltage regulator.
50Hz Operation200V
60Hz Operation220V
Turn the circuit breaker to ON position to send power to the load side.
Danger

<Caution>

￿Do not drive the starter motor for more than 10 seconds successively

￿If you need to restart, wait at least 30 seconds before the retry.

Release the starter switch, as soon as the engine is started

Keep the engine idle for at least 5 minutes

Set the throttle lever to RUN. Ensure that the frequency meter shows the following

 

frequency at no load.

 

 

<Caution>

 

No-load frequency(Revolution)

 

50Hz Operation

52.5Hz 1575min-1

 

 

 

 

60Hz Operation

63.0Hz1890min-1

 

 

 

 

 

 

 

￿In either case of incorrect frequency or frequency change, adjust the frequency by

FREQUENCY ADJUST SCREW.

￿By setting frequency to the above frequency under no load, 50 or 60Hz(almost) will be obtained at the rated output load.

￿ Before turning the circuit breaker to ON position to send power to the load side, always ensure that any circuit breaker and switch of loads are positioned to OFF.

￿ In the case the generator and the load are away from each other, proceed with the Above steps, communicating well with the other person by the load in order to prevent from accident.