10 | Jaguar Model |
JAGUAR J-390 NON-DIRECT VENT, VENTING THROUGH A ROOF
All joints must be liquid and pressure tight. Use 4” dia. PVC/CPVC schedule 40 pipe or U/L listed single wall 4" dia.
| 90°TERMINATION |
*ALTERNATE VERTICAL TERMINATION | ELBOW WITH SCREEN |
| |
45°ELBOW |
|
*RAIN CAP TERMINATION MAY BE USED | VENT TERMINATION |
TEE WITH SCREEN |
10 FT. MIN | 1 FT. MIN | |
FIRESTOP AND | FLASHING AND | |
SUPPORT | ||
STORM COLLAR | ||
| ||
| 2" MIN | |
| 4 IN. DIA. PVC/CPVC | |
| PIPE OR STAINLESS STEEL | |
| VENTING MATERIAL FOR VENT | |
SLOPE UP 1/4 IN. |
| |
PER FOOT MIN. |
| |
90°ELBOW | FIRESTOP AND | |
| SUPPORT | |
AIR INTAKE |
| |
(DO NOT BLOCK) |
| |
| 4 IN. DIA. PVC/CPVC | |
| PIPE OR STAINLESS STEEL | |
| VENTING MATERIAL FOR VENT |
Figure 8. Jaguar J-390 - non-direct vent, venting through the roof
* AL