Jaguar Model | 33 | |
|
|
|
VIEWING AND CHANGING SYSTEM SETTING - Table 5
“To change system setting or perform system test”
The menu is accessed by pressing and holding “SELECT” and “ENTER” buttons for 10 seconds. To change
system setting: Press “UP or DOWN” button, then press “ENTER”
WARNING: Only a trained, experienced service technician or installer should use this table.
Table 2 | Table 1 |
Table 2 | Table 1 |
Table 3
Table 1
Table 1
Tablle 1
Table 1
Table 3
Table 3
Table 3
Table 3
Table 3
Table 3
Table 3
Table 3
MODE DISPLAY | DESCRIPTION | |||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| * | Changing space heating post pump time. Settable from 10 to 900 seconds. | |
|
|
|
|
|
|
|
| |||
|
|
|
|
|
|
| (steps of 10 seconds). The default value is 30 seconds. | |||
|
|
|
|
|
|
|
| |||
|
| Table 3 |
| |||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| * | Changing DHW post pump time. Settable from 1 to 255 seconds. | |
Table 3 |
| |||||||||
| (steps of 1 seconds). The default value is 15 seconds. | |||||||||
| ||||||||||
|
|
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Changing space heating control mode |
|
|
|
|
|
|
|
|
| * | 0: Thermostat only (default) - boiler without outdoor sensor |
|
|
|
|
|
|
|
|
| 1: Outside sensor and Thermostat | |
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
| 2: Outside sensor only |
|
|
|
|
|
|
|
|
|
| 3: Permanent heat demand (boiler circulator always on) |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Changing domestic hot water (DHW) mode |
|
|
|
|
|
|
|
|
|
| 0: No DHW |
|
|
|
|
|
|
|
| * | 1: Storage tank with sensor | |
|
|
|
|
|
|
|
| 2: Storage tank with thermostat (default value) | ||
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
| 3: Plate heat exchanger |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Changing DHW or space heating priority mode |
|
|
|
|
|
|
|
| * | 0: DHW priority (no time limit) | |
|
|
|
|
|
|
|
| 1: Space heating priority (no time limit) | ||
Table 3 |
|
| 2: DHW priority for limited time (default) | |||||||
Table 3 |
|
| ||||||||
|
| 3: Space heating priority for limited time | ||||||||
|
|
|
|
|
|
|
|
|
| |
Tablle 3 |
|
|
| |||||||
Table 3 | * | Changing priority limited time. Settable from 20 to 80 minutes. | ||||||||
|
|
|
|
|
|
|
| |||
|
|
|
|
|
|
|
| The default value is 30 minutes. | ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| * | Boiler model selection, value is 5 for model | |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| * | Boiler model confirmation, value is 5 for model | |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| * | Weather compensation supply water reference temperature | |
|
|
|
|
|
|
|
| (space heating mode 1 or 2). Settable from 16˚F to 122˚F (steps of 1 F). | ||
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
| The default value is 86˚F. |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| * | Changing compensation slope (space heating mode 1 or 2). | |
|
|
|
|
|
|
|
| Settable from 0.1 to 5.0 (steps of 0.1). | ||
|
|
|
|
|
|
|
|
|
| The default value is 1.0. |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| * | Not Utilized | |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| * | Changing weather compensation set point (space heating mode 2 only). | |
|
|
|
|
|
|
|
| Settable from 32˚F to 122˚F (steps of 1˚F). | ||
|
|
|
|
|
|
|
|
|
| The default value is 68˚F. |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ** | Display shows blower RPM (mutiply reading by 10 for actual RPM) | |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| * | Change blower RPM for high input (steps of 30 RPM, limit +/- 480 RPM). | |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| * | Change blower RPM for low input (steps of 30 RPM, limit +/- 120 RPM). | |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ** | Display shows flame current in micro amps | |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| * | System test – Display shows flame current | |
|
|
|
|
|
|
|
| 0: System test off | ||
|
|
|
|
|
|
|
|
|
| L: Steady low input (20 minutes) |
|
|
|
|
|
|
|
|
|
| I: Steady ignition input (20 minutes) |
|
|
|
|
|
|
|
|
|
| H: Steady high input (20 minutes) |
|
|
|
|
|
|
|
|
|
|
|
NOTE: *: Alternating **: Steady