Jaguar Model J-390

33

 

 

 

VIEWING AND CHANGING SYSTEM SETTING - Table 5

“To change system setting or perform system test”

The menu is accessed by pressing and holding “SELECT” and “ENTER” buttons for 10 seconds. To change

system setting: Press “UP or DOWN” button, then press “ENTER”

WARNING: Only a trained, experienced service technician or installer should use this table.

Table 2

Table 1

Table 2

Table 1

Table 3

Table 1

Table 1

Tablle 1

Table 1

Table 3

Table 3

Table 3

Table 3

Table 3

Table 3

Table 3

Table 3

MODE DISPLAY

DESCRIPTION

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

*

Changing space heating post pump time. Settable from 10 to 900 seconds.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(steps of 10 seconds). The default value is 30 seconds.

 

 

 

 

 

 

 

 

 

 

Table 3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

*

Changing DHW post pump time. Settable from 1 to 255 seconds.

Table 3

 

 

(steps of 1 seconds). The default value is 15 seconds.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Changing space heating control mode

 

 

 

 

 

 

 

 

 

*

0: Thermostat only (default) - boiler without outdoor sensor

 

 

 

 

 

 

 

 

 

1: Outside sensor and Thermostat

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2: Outside sensor only

 

 

 

 

 

 

 

 

 

 

3: Permanent heat demand (boiler circulator always on)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Changing domestic hot water (DHW) mode

 

 

 

 

 

 

 

 

 

 

0: No DHW

 

 

 

 

 

 

 

 

*

1: Storage tank with sensor

 

 

 

 

 

 

 

 

2: Storage tank with thermostat (default value)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3: Plate heat exchanger

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Changing DHW or space heating priority mode

 

 

 

 

 

 

 

 

*

0: DHW priority (no time limit)

 

 

 

 

 

 

 

 

1: Space heating priority (no time limit)

Table 3

 

 

2: DHW priority for limited time (default)

Table 3

 

 

 

 

3: Space heating priority for limited time

 

 

 

 

 

 

 

 

 

 

Tablle 3

 

 

 

Table 3

*

Changing priority limited time. Settable from 20 to 80 minutes.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

The default value is 30 minutes.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

*

Boiler model selection, value is 5 for model J-390

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

*

Boiler model confirmation, value is 5 for model J-390

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

*

Weather compensation supply water reference temperature

 

 

 

 

 

 

 

 

(space heating mode 1 or 2). Settable from 16˚F to 122˚F (steps of 1 F).

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

The default value is 86˚F.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

*

Changing compensation slope (space heating mode 1 or 2).

 

 

 

 

 

 

 

 

Settable from 0.1 to 5.0 (steps of 0.1).

 

 

 

 

 

 

 

 

 

 

The default value is 1.0.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

*

Not Utilized

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

*

Changing weather compensation set point (space heating mode 2 only).

 

 

 

 

 

 

 

 

Settable from 32˚F to 122˚F (steps of 1˚F).

 

 

 

 

 

 

 

 

 

 

The default value is 68˚F.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

**

Display shows blower RPM (mutiply reading by 10 for actual RPM)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

*

Change blower RPM for high input (steps of 30 RPM, limit +/- 480 RPM).

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

*

Change blower RPM for low input (steps of 30 RPM, limit +/- 120 RPM).

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

**

Display shows flame current in micro amps

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

*

System test – Display shows flame current

 

 

 

 

 

 

 

 

0: System test off

 

 

 

 

 

 

 

 

 

 

L: Steady low input (20 minutes)

 

 

 

 

 

 

 

 

 

 

I: Steady ignition input (20 minutes)

 

 

 

 

 

 

 

 

 

 

H: Steady high input (20 minutes)

 

 

 

 

 

 

 

 

 

 

 

NOTE: *: Alternating **: Steady

Page 33
Image 33
Slant/Fin installation instructions Boiler model selection, value is 5 for model J-390