24 | Jaguar Model |
WATER PIPING
1.Connection of system to boiler:
Primary/secondary piping of the system is recommended, to ensure the proper flow through the boiler. (See Figures 19 through 21). The boiler loop piping must be the same diameter as the water outlet (supply) and inlet (return) piping connections provided on the boiler, particularly on longer loops. See page 2 for piping connection size.
2.Circulator Pumps:
The boiler loop piping must utilize the Taco
3.Relief Valve(supplied with boiler):
Tee the relief valve into the boiler water outlet (supply) piping as close to the water outlet (supply) connection as possible. (See Figure 17). The relief valve’s discharge piping must be the same size or larger than the relief valve’s outlet, and must terminate 6” minimum from floor with a plain (no threads) end. Place a bucket under pressure relief valve discharge. Make sure discharge is always visible. DO NOT
4.Air Control System:
An appropriately sized
5.Cold Water Fill:
A pressure reducing (fill) valve, with a
6.Low Water Cutoff:
On a hot water boiler installed above radiation level, the boiler must be provided with a low water cutoff device at the time of installation by the installer (see Figure 17 for piping arrangement).
7.Water Treatment and Freeze Protection:
A good water treatment program will not only extend the useful life of this boiler but it will also save much of the time and expense of repairs made necessary by preventable occurrences. A reputable water treatment company should be consulted to evaluate and determine the best overall treatment program for your boiler equipment.
The heat exchanger is made of aluminum, so the system water must be maintained between 7.0 and 8.5 PH level. Thoroughly flush the system, before connecting the boiler, to remove any sediment or glycol.
Never use Ethylene Glycol as it is toxic to humans.
Never use any types of automotive or standard gylcol freeze protection fluids.
8.Piping a heating - cooling system to a water boiler and chiller:
Figure 21 illustrates a method of piping a heating-cooling system to a water boiler and a chiller. Hand valves (shown) or automatic valves must be installed to prevent circulation of chilled water in the boiler or hot water in the chiller.
The air control system and pressure control system must operate with chiller only, or the boiler only, being valved to the piping system. Separate control devices on the boiler and chiller may be used, or a single set of air and pres- sure controls on the common piping may be preferred.
If the boiler is used to supply hot water to heating coils in air handling units, flow control valves or other devices must be installed to prevent gravity circulation of water in the coils during the cooling cycle.