Jaguar Model J-390

39

 

 

 

B.BLOCKING ERRORS: Indicated by an “E” in the mode display. Operation is automatically restored, once the condition returns to normal or is fixed. The temperature display shows the error code. Pressing the “Reset” button is not required.

ERROR CODE

INDICATION

REMEDY

 

 

 

01

 

Check wire harness connections going to the

Water Outlet Sensor Open

sensor.

 

 

Replace the sensor.

 

 

 

02

 

Check wire harness connections going to the

Water Inlet Sensor Open

sensor.

 

 

Replace the sensor.

 

 

 

03

Flue Gas Sensor Open

Check wire harness connections going to the

sensor.

 

 

Replace the sensor.

 

 

 

11

Water Outlet Sensor Shorted

Replace the sensor.

 

 

 

12

Water Inlet Sensor Shorted

Replace the sensor.

 

 

 

13

Flue Gas Sensor Shorted

Replace the sensor.

 

 

 

19, 42, 45,

 

Replace control board. Make sure the proper

Control Failure

boiler model selection and confirmation code is

46, 47, 48

 

entered. See Table 5 on page 33.

 

 

 

 

 

If a flame is still observed after a call for heat is

20

Flame Detected at Wrong Time

stopped, replace the gas valve, If the burner

seems to be shutting down properly, replace the

 

 

 

 

spark ignitor.

 

 

 

21

Polarity Error

Reverse the hot and neutral power supply wires.

 

 

 

22

 

Check power supply frequency to be 60 hz,

Frequency Error

certain power supplies may not provide the

 

 

proper frequency.

 

 

 

24

Earth Connection Faulty

Check grounding of control and boiler chassis.

 

 

 

continued on page 39