6

Jaguar Model J-390

For both direct and non-direct installation, the following must be considered:

- Openings must never be reduced or closed. If doors or win- dows are used for air supply, they must be locked open.

-Protect against closure of openings by snow and debris. Inspect frequently.

-No mechanical draft exhaust or supply fans are to be used in or near the boiler area.

-Boiler area must never be under negative pressure. The flow of combustion and ventilating air to the boiler must not be obstructed.

FLUE GAS VENTING REQUIREMENTS

The Jaguar J-390 series boiler is a high efficiency, mechanical- ly forced draft boiler and, therefore, require different venting arrangements than natural draft, lower efficiency boilers.

THE FOLLOWING INSTRUCTIONS MUST BE CAREFULLY READ AND FOLLOWED IN ORDER TO AVOID ANY HAZ- ARDOUS CONDITIONS DUE TO IMPROPER INSTALLATION OF THE AIR INTAKE AND FLUE GAS VENTING SYSTEM.

The vent piping installation MUST be in accordance with these instructions and with ANSI Z223.1-latest edition NATIONAL FUEL GAS CODE, Part 7, Venting of Equipment. Other local codes may also apply and must be followed. Where there is a conflict between these requirements, the more stringent case shall apply.

The use of a vent damper is NOT permitted on this boiler series.

ADDITIONAL REQUIREMENTS FOR THE COMMONWEALTH OF MASSACHUSETTS

When the Bobcat is installed and used in the Commonwealth of Massa- chusetts, the following additional requirements pursuant to Massachusetts code 248 CMR MUST be met:

(1). Exisiting chimneys shall be permitted to have their use continued when a gas conversion burner is installed, and shall be equipped with a manual reset device that will automatically shut off gas to the burner in the event of a sustained back-draft.

(2)(a). For all side wall horizontally vented gas fueld equipment installed in every dwelling, building or structure used in whole or part for residential purposes, including those owned or operated by the Commonwealth and where the side wall exhaust vent termination is less than seven (7) feet above finsihed grade in the area of the venting, including but not limited to decks and porches, the following requirements shall be satisfied:

1.INSTALLATION OF CARBON MONOXIDE DETECTORS. At the time of installation of the side wall horizontal vented fueled equipment, the installing plumber or gasfitter shall observe that a hard wired carbon monoxide detector with an alarm and battery back-up is installed on the floor level where the gas equipment is to be installed. In addition, the installing plumber or gasfitter shall observe that a battery operated or hard wired carbon monoxide detector with an alarm is installed on each addi- tional level of the dwelling, building or structure served by the side wall horizontal vented gas fueled equipment. It shall be the responsibility of the property owner to secure the services of qualified licensed professionals for the installation of hard wired carbon monoxide detectors.

a.In the event that the side wall horizontally vented gas fueld equipment is installed in a crawl space or an attic, the hard wired carbon monoxide detector with alarm and battery back up may be installed on the next adja- cent floor level.

b.In th event that the requirements of this subdivision can not be met at the time of completion of installation, the owner shall have a period of thir- ty (30) days to comply with the above requirements; provided, however, that during said thirty (30) day period, a battery operated carbon monoxide detector with an alarm shall be installed.

2.APPROVED CARBON MONOXIDE DETECTORS. Each carbon

monoxide detector as required in accordance with the above provisions shall comply with NFPA 720 and be ANSI/UL 2034 listed and IAS certified.

3.SIGNAGE. A metal or plastic identification plate shall be permanently mounted to the exterior of the building at a minimum height of eight (8) feet above grade directly in line with the exhaust vent terminal for the hori- zontally vented gas fueled heating appliance or equipment. The sign shall read, in print size no less that one-half (1/2) inch in size, “GAS VENT

DIRECTLY BELOW, KEEP CLEAR OF ALL OBSTRUCTIONS”.

4.INSPECTION. The state or local gas inspector of the side wall horizon- tally vented gas fueled equipment shall not approve the installation unless, upon inspection, the inspector observes carbon monoxide detectors and signage installed in accordance with the provisions of 248 CMR 5.08(2)(a)1 through 4.

(b)EXEMPTIONS. The following equipment is exempt from 248 CMR 5.08(2)(a)1 through 4:

1.The equipment listed in Chapter 10 entitled “Equipment Not Required TO Be Vented” in the most current edition of NFPA 54 as adopted by the Board; and

2.Product Approved side wall horizontally vented gas fueled equip- ment installed in a room or structure separate from the dwelling, build- ing or structure used in whole or part for residential purposes.

VENT AND AIR INTAKE MATERIALS

The vent and air intake system for direct or non-direct vent installation must be 4” diameter PVC/CPVC schedule. 40 pipe, or UL listed single wall 4” diameter AL29-4C* stainless steel material. The following manufacturers’ systems are approved for use within a specified minimum and maximum equivalent

vent length in this manual.

Manufacturer

Type/System

Sealant

 

 

 

Heat-Fab. Inc.

Saf-T Vent

Not Required

EZ Seal

 

 

 

 

 

ProTech System,

FasNSeal

Not Required

Inc.

 

 

 

 

 

Flex-L International

StaR-34

GE-IS806

Inc.

 

 

 

 

 

Z-Flex, Inc.

Z-Vent

GE, RTV 106

 

 

 

Metal-Fab, Inc.

Corr Guard

Not Required

 

 

 

N/A

PVC pipe,

PVC primer

Schedule 40

and cement

 

 

 

 

N/A

CPVC pipe,

CPVC primer

Schedule 40

and cement

 

 

 

 

When joining the various components of the listed stainless steel vent systems, the manufacturers’ instructions should be closely fol- lowed to insure proper sealing. Use sealant specified by vent sys- tem manufacturer for sealing of pipe and fittings, if required. When joining the PVC/CPVC pipe and fittings, follow the instructions pro- vided in this manual. All connections must be liquid and pressure tight. DO NOT use galvanized flue pipe or any plastic-type materi- als other than PVC/CPVC Schedule 40.

Page 6
Image 6
Slant/Fin J-390 installation instructions Flue GAS Venting Requirements, Vent and AIR Intake Materials