State Industries SBD71 120 Sbd Sequence Of Operation, Thermostat calls for heat, Main and pilot

Models: SBD85 500 SBD71 120

1 56
Download 56 pages 57.8 Kb
Page 17
Image 17
SBD SEQUENCE OF OPERATION

SBD TANK TYPE HEATERS

SERVICE HANDBOOK

SBD SEQUENCE OF OPERATION

1.Thermostat calls for heat

7.Thermostat satisfies

3.Intermittent Ignition Control

9.Flue damper closes

2.Flue damper opens

4.Pilot gas opens, Pilot sparks and flame proves

6. Main burner ignites

5. Main gas valve opens

8. Main and pilot

 

burners "OFF"

SEQUENCE OF OPERATION

To understand SBD tank type water heaters, an examination of their sequence of operation is necessary.

When the thermostat calls for heat, the relay in the draft hood assembly activates the flue damper motor. The damper opens and power flows to the IID (Intermittent Ignition Device). This activates the IID module to open the pilot valve and begin sparking at the pilot burner assembly. Once the pilot flame is established and confirmed back to the IID, the sparking is stopped and the main gas valve is opened, allowing gas flow to the main burner. When the thermostat satisfies, main and pilot gas is shut off. Damper is returned to closed position.

Technical Training Department

16

Ashland City, TN ©2003

Page 17
Image 17
State Industries SBD71 120 Sbd Sequence Of Operation, Thermostat calls for heat, Thermostat satisfies, Main burner ignites