THERMOSTAT TEST

SBD TANK TYPE HEATERS

SERVICE HANDBOOK

STEP 7

THERMOSTAT TEST

STEP 7. THERMOSTAT TEST. Set the thermostat to call for heat. Using your multimeter, test for 24 VAC between right terminal and ground.

IF

THEN

The meter does not read 24 VAC and the jumper wire

Replace the thermostat

between the high limit and the thermostat is in place:

 

 

The meter reads 24 VAC:

Go to step 8.

Note: If the high limit to thermostat jumper wire was disconnected earlier to simulate a satisfied thermostat, reconnect the jumper to the terminals.

Note: A yellow wire from this thermostat terminal connects to the damper PC board.