VERTICAL DUCTS

SBD TANK TYPE HEATERS

SERVICE HANDBOOK

MAKE-UP AIR

VERTICAL DUCTS

1Square Inch Per 4,000 BTUH

Often it is more practical to install vertical make-up air ducts to the out doors. Again, two openings are required - one within 12 inches of the top of the enclosure and one within twelve inches of the bottom of the enclosure. Each opening shall have a free area of not less than 1 square inch per 4000 BTUH of the total input of all appliances within the enclosure.

MAKE-UP AIR

HORIZONTAL DUCTS

1 Square

Inch Per

2,000 BTUH

When the heater is installed in an interior room with no roof access for vertical ducts, horizontal make-up air ducts should be installed. When using horizontal ducts, two openings are required - one within 12 inches of the top of the enclosure and one within twelve inches of the bottom of the enclosure. Each opening shall have a free area of not less than 1 square inch per 2000 BTUH of the total input of all appliances within the enclosure.