SBD TANK TYPE HEATERS
SERVICE HANDBOOK
STEP 17
IID MODULE TEST
Pilot is lit - Sparking has stopped.
STEP 17. IID MODULE TEST (Power to the Main Valve). Using a multimeter, test for 24 VAC between terminal MV on the IID and 24V (GND).
IF |
| THEN | |
24 | VAC is not present: | • | Replace the IID module. Conduct Step |
|
|
| 18 before applying power to |
|
|
| replacement module. |
24 | VAC is present: | • | Go to step 18. |