S U F S E R V I C E H A N D B O O K
T R O U B L E S H O O T I N G
GAS PRESSURE CHECK
STEP 13
SUPPLY GAS PRESSURE TEST
SUF 150, 199 | SUF 150, 199 |
Propane | Natural |
SUF 240 Natural | Gas Valve |
Gas Valve |
|
STEP 13: CHECK AND ADJUST SUPPLY GAS PRESSURE.
Attach manometer or gas pressure gauge to pressure tap on gas valve or use adapter to check pressure ahead of valve as near as possible to valve. All appliances being served by this gas sup- ply line should be operating.
IF... | THEN |
|
|
|
|
supply gas pressure is not between 5.0 and 14” W.C. | adjust supply gas pressure (Recommended supply |
natural gas or 11.0 and 14” W.C. propane | minimum is 7.0” W.C. for natural gas models) |
|
|
proper supply gas pressure is present | continue to Step 14. |
|
|
STEP 14
MANIFOLD GAS PRESSURE TEST
STEP 14: CHECK AND ADJUST MANIFOLD GAS PRESSURE.
IF... | THEN | |
|
| |
|
| |
manifold gas pressure is not: | adjust manifold gas pressure to values given for model | |
natural gas models | and fuel type (within 0.3” W.C. tolerance) | |
if manifold gas pressure cannot be adjusted to | ||
3.5” W.C. ± 0.3” – SUF 155 & 199 | ||
maintain values given (within 0.3” W.C. tolerance) | ||
4.0” W.C. ± 0.3” – SUF 240 | ||
replace gas valve. | ||
propane gas models | ||
| ||
10.0” W.C. ± 0.3” – all propane gas models. |
| |
|
| |
manifold gas pressure is within tolerances given above | ignition should occur. | |
|
|
State Water Heaters | 31 | Technical Training Department |
Ashland City, Tennessee © 2004 |