S U F S E R V I C E H A N D B O O K

T R O U B L E S H O O T I N G

GAS PRESSURE CHECK

STEP 13

SUPPLY GAS PRESSURE TEST

SUF 150, 199

SUF 150, 199

Propane

Natural

SUF 240 Natural

Gas Valve

Gas Valve

 

STEP 13: CHECK AND ADJUST SUPPLY GAS PRESSURE.

Attach manometer or gas pressure gauge to pressure tap on gas valve or use adapter to check pressure ahead of valve as near as possible to valve. All appliances being served by this gas sup- ply line should be operating.

IF...

THEN

 

 

 

 

supply gas pressure is not between 5.0 and 14” W.C.

adjust supply gas pressure (Recommended supply

natural gas or 11.0 and 14” W.C. propane

minimum is 7.0” W.C. for natural gas models)

 

 

proper supply gas pressure is present

continue to Step 14.

 

 

STEP 14

MANIFOLD GAS PRESSURE TEST

STEP 14: CHECK AND ADJUST MANIFOLD GAS PRESSURE.

IF...

THEN

 

 

 

 

manifold gas pressure is not:

adjust manifold gas pressure to values given for model

natural gas models

and fuel type (within 0.3” W.C. tolerance)

if manifold gas pressure cannot be adjusted to

3.5” W.C. ± 0.3” – SUF 155 & 199

maintain values given (within 0.3” W.C. tolerance)

4.0” W.C. ± 0.3” – SUF 240

replace gas valve.

propane gas models

 

10.0” W.C. ± 0.3” – all propane gas models.

 

 

 

manifold gas pressure is within tolerances given above

ignition should occur.

 

 