State Industries STC-077 dimensions SUF Muffler, T E S

Models: STC-077

1 46
Download 46 pages 13.03 Kb
Page 38
Image 38

S U F S E R V I C E H A N D B O O K

S E R V I C E A I D S

SUF MUFFLER

N O T E S :

1.Install muffler in vertical position only.

2.Muffler must be a minimum of 8” from top of condensate elbow.

3.The muffler inlet and outlet are 4” PVC. If venting with a 4” PVC, a 4” x 4” PVC coupling (field supplied) must be cemented to each end of the muffler. If venting with 3” PVC, a 4” x 3” PVC reducing coupling (field supplied) must be cemented to each end of muffler (see illustration above.)

4.Cement muffler into a location using ASTM D-2564 grade cement.

5.Secure muffler to suitable structure.

6.Operate heater through 1 heat cycle to ensure there are no exhaust leaks and there is no obstruction of exhaust flow.

State Water Heaters

37

Technical Training Department

Ashland City, Tennessee © 2004

STC-077

Page 38
Image 38
State Industries STC-077 dimensions SUF Muffler, T E S