Configuration Planning

Power Requirements

Table 2-9. VSM5-VTSS Power Requirements — Single AC Source Power Cable Operation

Number of

AC Source

AC Source

kVA

kW

Power

kBTUs

16-Drive Arrays

Voltage In

Amps (Current) In

Factor

Per Hour

 

 

 

264V

10.1A

2.7

2.5

0.95

8.6

 

 

 

 

 

 

 

2

208V

12.4A

2.6

2.5

0.98

8.6

 

 

 

 

 

 

 

 

180V

16.2A

2.9

2.9

0.99

9.9

 

 

 

 

 

 

 

 

264V

13.0A

3.4

3.3

0.95

11.1

3

208V

16.0A

3.3

3.3

0.98

11.1

 

180V

18.3A

3.3

3.3

0.99

11.1

 

264V

14.5A

3.8

3.6

0.95

12.4

 

 

 

 

 

 

 

4

208V

17.8A

3.7

3.6

0.98

12.4

 

 

 

 

 

 

 

 

180V

20.3A

3.7

3.6

0.99

12.4

 

 

 

 

 

 

 

Notes:

• Abbreviations key: A = ampere(s); AC = alternating current; kBTUs = thousand British Thermal Units; kVA = kilovolt-amperes; kW = kilowatts

Table 2-10. VSM5-VTSS Power Requirements — Dual AC Source Power Cable Operation

Number of

AC Source

AC Source

kVA

kW

Power

kBTUs

16-Drive Arrays

Voltage In

Amps (Current) In*

Factor

Per Hour

 

 

 

264V

5.6A

3.0

2.8

0.95

9.6

 

 

 

 

 

 

 

2

208V

6.9A

2.9

2.8

0.98

9.6

 

 

 

 

 

 

 

 

180V

7.9A

2.8

2.8

0.99

9.6

 

 

 

 

 

 

 

 

264V

6.3A

3.3

3.1

0.95

10.7

3

208V

7.7A

3.2

3.1

0.98

10.7

 

180V

8.8A

3.2

3.1

0.99

10.7

 

264V

6.9A

3.7

3.5

0.95

11.9

 

 

 

 

 

 

 

4

208V

8.5A

3.5

3.5

0.98

11.9

 

 

 

 

 

 

 

 

180V

9.8A

3.5

3.5

0.99

11.9

 

 

 

 

 

 

 

Notes:

* Values are for each line cord; multiply this value by two to obtain the total current for both line cords.

• Abbreviations key: A = ampere(s); AC = alternating current; kBTUs = thousand British Thermal Units; kVA = kilovolt-amperes; kW = kilowatts

2-42

Sun Confidential: Internal Only

96257

 

Revision A

 

Page 42
Image 42
Sun Microsystems 96257 manual Power Requirements