Sun Microsystems 96257 Raised-Floor Lateral Stability Ratings, Raised-Floor Panel Ratings, 92.1

Models: 96257

1 118
Download 118 pages 44.52 Kb
Page 54
Image 54
92.1 (36.26)

Site Readiness Planning

Figure 4-3. VSM5-VTSS Cabinet Weight Distribution and Leveler Locations

92.1 (36.26)

47.11

(18.55)

(2X)

6.29(2.725)

(2X)

6.29

(2.725)

(2X)

97.40

 

 

Z

75.01

 

 

 

 

 

(261)

 

 

 

(201)

 

 

 

 

 

 

X

 

 

 

 

 

X

77.1

 

 

 

 

 

 

 

 

109.72

 

 

 

84.34

(30.35)

 

 

 

 

 

 

 

 

 

 

 

(294)

 

 

 

 

 

 

 

 

 

 

 

 

Z

(226)

 

 

 

 

14.98

 

 

 

 

 

 

 

 

 

 

77.59 (30.55)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(2X)

 

 

 

(5.90)

 

 

 

 

 

 

 

 

 

 

 

 

(2X)

 

 

 

 

 

 

 

 

 

 

 

 

A504 026

Raised-Floor Lateral Stability Ratings

In areas of high earthquake activity, the lateral stability of raised floors must be consid- ered. Raised floors where VSM5 system equipment is installed must be able to resist the horizontal-stress levels shown in Table 4-5.

Table 4-5. Raised Flooring Horizontal Force Chart

Seismic Risk Zone

Horizontal Force (V) Applied at Top of Pedestal

1

13.5 kg / 29.7 lbs

 

 

2A

20.2 kg / 44.6 lbs

2B

26.9 kg / 59.4 lbs

 

 

3

40.4 kg / 89.1 lbs

4

53.9 kg / 118.8 lbs

 

 

Note: Note: Horizontal forces are based on the 1991 Uniform Building Code (UBC) Sections 2336 and 2337, and assume minimum operating clearances for multiple VSM5 cabinets. Installations in areas not covered by the UBC should be engineered to meet seismic code provisions of the local jurisdiction.

Raised-Floor Panel Ratings

Raised floor panels must be able to resist a concentrated load of 454 kg (1000 lbs.) and a rolling load of 181 kg (400 lbs.) anywhere on the panel with a maximum deflection of 2 mm (0.08 in.). Perforated floor panels are not required for VSM5 system equipment, but if used must comply with the same ratings.

4-54

Sun Confidential: Internal Only

96257

 

Revision A

 

Page 54
Image 54