SA-SB-01 INTERFACE CONNECTIONS

TO SA41 INVERTER

 

 

+48V

 

FOR ALARM INPUT

 

 

 

APPLICATIONS,

 

 

SA-SB-01

REFER BELOW EXAMPLES

 

 

INTERFACE BOARD

 

RELAY-SPDT

TOP VIEW

 

 

 

 

RELAY-SPDT

+48V (INT FUSE)

1

 

ALARM INPUTS

IN 2

2

 

IN 1

3

 

 

 

 

0V

4

BLK

 

GRN

 

DO-

5

 

BLU

 

D0+

6

 

WH

DB25-M

RIN-

7

YELL

RIN+

8

RED

 

 

 

+12V

9

 

 

INV-

10

SHIELD

 

BATT-

11

 

 

OUT 2

12

50mA MAX

CONTROLLER

50mA MAX

OUT 1

13

OUTPUTS

1A FUSE INSIDE INVERTER

+48V

14

 

 

INVERTER -

 

-

+

CHARGER -

SA-S200

48V

 

 

 

ALL CHARGING

200 AMP 75mV

BATTERY

AND DISCHARGING

CURRENT SHUNT

 

 

SOURCES, NEG LEAD

 

 

 

 

 

 

 

GROUND

 

REAR VIEW

SA-KP-01

KEYPAD

1

RED

BLK

2

YELL

3

WH

4

BLU

5

GRN

6

 

 

TO INVERTER POSITIVE

 

FUSE BATTERY NEGATIVE

SYSTEM

FUSE

IF IT IS NOT EARTHED

Figure 1

ALARM INPUTS - Examples

(Alarm input 1 shown only)

ALARM FITTED TO BATTERY ROOM DOOR

REED SWITCH (NORMALLY CLOSED)

+48V 1

IN2 2

IN1 3

SET ALARM INPUT 1 = LO

Figure 2.1

Figure 2

GENERATOR OIL PRESSURE MONITOR

+48V

1

 

 

 

LAMP

IN2

2

 

IN1

3

OIL

 

 

PRESS

 

 

SWITCH

0V

4

 

SET ALARM INPUT 1 = HI

Figure 2.3

NORMALLY OPEN

+48V 1

IN2 2

IN1 3

SET ALARM INPUT 1 = HI

Figure 2.2

MONITORING OF SWITCH CLOSURE WHERE ONE SIDE COMMITTED TO EARTH

+48V

1

 

IN2

2

4.7K 2W

 

IN1

3

 

0V 4

SET ALARM INPUT 1 = LO

Figure 2.4

26

Page 26
Image 26
Toro SA41 owner manual SA-SB-01 Interface Connections, Alarm Inputs Examples