3. Important Safety Instructions

This manual contains important instructions that should be followed during the installation and maintenance of the UPS and its batteries.

Hardwired UPS units are not equipped with an over-current protection device nor an output disconnect for the AC output. A circuit breaker should be provided by the user between the UPS output and the load input. This device should be rated as follows:

240VAC

3.6 kVA

6 kVA

8 kVA

10 kVA

14 kVA

18 kVA

22 kVA

RATING

20 A

35 A

45 A

60 A

80 A

100 A

125 A

* Ratings are for an 80% rated device.

The nominal battery voltages for these models are as follows:

BATTERY

3.6 kVA

6 kVA

8 kVA

10 kVA

14 kVA

18 kVA

22 kVA

VOLTAGE

144 Vdc

216 Vdc

288 Vdc

288 Vdc

288 Vdc

288 Vdc

288 Vdc

Servicing of the batteries should only be performed by a qualified factory authorized representative who is knowledgeable about batteries and the required precautions. Keep unauthorized personnel away from batteries. To arrange for battery replacement, contact Toshiba Customer Support Center.

1.Turn off, lockout, and tagout all equipment before connecting the power wiring to the equipment or when performing maintenance.

2.The maximum ambient operating temperature is 104 °F (40 °C).

3.Access panels should only be removed by authorized Toshiba field Service personnel.

4.UPS servicing should be performed by qualified Toshiba representatives only.

5.Battery servicing should be performed by qualified Toshiba representatives only.

6.Contact your Toshiba authorized service center for battery replacement.

1600XP Series Installation and Operation Manual

5

Page 15
Image 15
Toshiba 1600XP operation manual Important Safety Instructions, 20 a, 45 a 60 a 80 a 100 a 125 a, Vdc 216 Vdc 288 Vdc