1600XP Series Installation and Operation Manual
1600XP Command Parameters Table
Cmd | Description | Brief Description | Location Map | Example | Rqd Security | By | |
ID | on LCD |
|
|
|
| Level to change |
|
| Tab | Block |
|
| |||
222 | VOOV De- | Output Overvoltage Detection Level in percent- | Setting | OUT | 110 % | Nonchangeable | User |
| Level* | age |
|
|
| Nonchangeable | Administrator |
|
| - Of rated output voltage which was configured |
|
|
| Changeable | Service |
|
| with Command ID215 |
|
|
|
|
|
|
|
|
|
|
|
|
|
224 | Fo Syn Win- | Output Frequency Synchronization Window | Setting | OUT | 1.0 Hz | Nonchangeable | User |
| dow* |
|
|
|
| Nonchangeable | Administrator |
|
|
|
|
|
| Changeable | Service |
|
|
|
|
|
|
|
|
225 | Fo Slew Rate | Output Frequency Slew Rate | Setting | OUT | 10 | Changeable | Service |
|
|
|
|
|
|
|
|
226 | Vout Adjust | Output Voltage Adjustment | Setting | OUT | 0 | Nonchangeable | User |
|
| - Can adjust up to +/- 5 increment of one in |
|
|
| Changeable | Administrator |
|
| order to increase or decrease output voltage to |
|
|
| Changeable | Service |
|
| compensate line voltage drop. |
|
|
|
|
|
|
|
|
|
|
|
|
|
227 | Iout 100% | Output Current 100% Amount | Setting | OUT | 250 | Changeable | Service |
| Amount |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
228 | OOL Delevel | Output Overload Warning/Fault Detection Level | Setting | OUT | 110 | Changeable | Service |
|
| in percentage |
|
|
|
|
|
|
|
|
|
|
|
|
|
229 | OOL DeDelay | Output Overload Warning/Fault Detection De- | Setting | OUT | 30 | Changeable | Service |
|
| lay at 125% @25° |
|
|
|
|
|
|
|
|
|
|
|
|
|
230 | OOL ReLevel | Output Overload Warning Recovery Delay | Setting | OUT | 105 | Changeable | Service |
|
|
|
|
|
|
|
|
231 | OOL ReDelay | Output Overload Warning Recovery Delay | Setting | OUT | 160 | Changeable | Service |
|
|
|
|
|
|
|
|
232 | Vout Comp. | Output Voltage will be compensated according | Setting | OUT | 20 | Changeable | Service |
| Step | to this setup and current percentage |
|
|
|
|
|
|
|
|
|
|
|
|
|
233 | Vout Gain | Use this value to convert AD value to Actual | Setting | OUT | 7987 | Changeable | Service |
|
| Value |
|
|
|
|
|
|
|
|
|
|
|
|
|
234 | Vout Offset | Feedback Offset adjustment due to hardware | Setting | OUT | 0 | Changeable | Service |
|
| and software components |
|
|
|
|
|
|
|
|
|
|
|
|
|
242 | Iout Gain | At 240VAC use this value to convert AD VAlue | Setting | OUT | 1131 | Changeable | Service |
|
| to Actual Value |
|
|
|
|
|
|
|
|
|
|
|
|
|
243 | Iout Offset | Feedback Offset adjustment due to hardware | Setting | OUT | 0 | Changeable | Service |
|
| and software compenents. |
|
|
|
|
|
|
|
|
|
|
|
|
|
251 | Vref PhAdj | Time delay adjustment to sync the actual phase | Setting | OUT | Changeable | Service | |
| 60Hz | of output and plotting. |
|
|
|
|
|
|
|
|
|
|
|
|
|
254 | Vref Amplitude | Calibrated no Load Output Voltage | Setting | OUT | 246 | Changeable | Service |
|
|
|
|
|
|
|
|