Toshiba 1600XP operation manual Screen Tab Settings, Key Cmd ID range Types of Parameters

Models: 1600XP

1 100
Download 100 pages 60.45 Kb
Page 44
Image 44

17. Screen Tab: Settings

The tables on pages A1 - A14 list the 1600XP Settings parameters that can be viewed in the MONITOR tab.

Example: The Settings parameter Batt Test Freq (Battery Test Frequency) can be viewed by USR (User) level and above, only logged in ADM (Administrators) and above can edit the value.

Each key displays a block of relevant command parameters:

Key – (Cmd ID range)

Types of Parameters

 

 

 

ID – (000-099) UPS specific information such as serial number, software versions, installation date.

Input – (100-199) Input measured/calculated data such as input voltage, frequency, current, power, over-/under- voltage settings.

Output – (200-299) Output measured/calculated data such as output voltage, frequency, current, power, over-/under- voltage settings.

Bypass – (300-399) Bypass data such as configuration, voltage, current, power, OV detection level.

DC Bus – (400-499) Data such as Total voltage, rated voltage, Positive and Negative bus voltages.

Batt – (500-599) Battery voltage, charger status, total discharges, shutdown voltage.

Ctrl/Cfg – (600-699) Control and configuration list system and battery temperatures, system status, startup delay, auto-transfer window, restart mode.

History – (700-799) History lists metrics like system operation time, total over loads, hi system temp.

Disp/Reye – (800-849) Display specific parameters like Disp. Firmware version, sleep timer, buzzer status, display calibration points, and RemotEye III settings.

(850-859) lists RemotEye III IP address, IP Mask, Status, Baud Rate, datalink status.

96%

100%

INV

12:35 PM

HOME

USR

 

 

Main

Monitor

Settings

Records

 

ID

Input

Output

Bypass

DC Bus

Batt

 

Ctrl/Cfg

History

Disp/Reye

Debug

 

 

 

On-Line

SETTINGS OPENING SCREEN

34

1600XP Series Installation and Operation Manual

Page 44
Image 44
Toshiba 1600XP operation manual Screen Tab Settings, Key Cmd ID range Types of Parameters