Toshiba operation manual Appendix a 1600XP Specifications, Standard Model 3.6 10 kva

Models: 1600XP

1 100
Download 100 pages 60.45 Kb
Page 67
Image 67

Appendix A: 1600XP Specifications

Standard Model: 3.6 – 10 kva

Unit (Capacity)

3.6kVA (3.1 kW) 1

6 kVA (5.1 kW) 1

8 kVA (6.8 kW) 1

10 kVA (8.5 kW) 1

General

Topology

 

 

True On-Line

 

 

Certifications

ANSI C62.41 (IEEE 587), UL 1778, CUL, CE, FCC Class A , NEC (NFPS-70), NEMA/

PE1-1993, OSHA, ASME, ISO 9001, ISO 14001:2004 , RoHS Compliant

 

Input Characteristics

 

 

 

 

 

 

 

Input Voltage1

 

 

Single-phase, 208/240 Vac, +10% to -30%1

Input Frequency

 

 

45 – 65 Hz (auto-sensing)

 

 

Input Capacity

3.6 kVA

 

6 kVA

 

8.0 kVA

 

10 kVA

Input /(Max Input) Current @208V

17.9 (18.7) A

 

29.8 (31.1) A

 

38.9 (40.5) A

 

48.6 (50.2) A

Input/(Max. Input) Current @240V

15.5 (16.2) A

 

25.9 (27.0) A

 

33.7 (35.1) A

 

42.1 (43.5) A

Input Power Factor

 

 

0.98 Typical, 0.95 Minimum@ 100% Load

Current THD (linear load)

 

 

< 5% total harmonic distortion

 

 

Internal AC Input Breaker Rating

30 A/277 V

 

50 A/277 V

 

60 A/277 V

 

63 A/277 V

Battery Characteristics

 

 

 

 

 

 

 

Battery Type

 

Valve Regulated Lead Acid, Flame Retardant

Backup time, fully charged @ 0.7

8 min.2

 

8 min.2

 

7 min.2

 

7 min.2

power factor, 77 °F

 

 

 

 

 

 

 

 

 

 

Backup time, fully charged @ 0.85

7 min.2

 

7 min.2

 

7 min.2

 

5 min.2

power factor, 77 °F

 

 

 

 

 

 

 

 

 

 

Recharge Time

 

24 hr. (full), 12 hr. (90%) for internal batteries only3

Battery Voltage (Nominal)

144 Vdc

 

216 Vdc

 

 

288 Vdc

Output Characteristics

 

 

 

 

 

 

 

Output Voltage

 

 

Single-phase, 240/208/120 V

 

 

Output Voltage Regulation

 

 

 

= ± 3%

 

 

Output Frequency

±0.5 Hz/1.0 Hz/1.5 Hz (factory or authorized service center selectable only)

AUTO/MAN Frequency

 

Factory or authorized service center selectable only

Voltage THD

 

< 3% for linear load; < 6% for non-linear load

Common-Mode Noise

 

 

< 0.5 Vrms

 

 

Rated Load Power Factor1

 

 

0.85 (0.6 – 1.0) lagging

 

 

Efficiency (ac-dc-ac)

 

≥83%

 

 

>85%

Voltage Transient

 

 

< ±8% (Load of 0 – 100 %)

 

 

Voltage Transient Recovery

 

 

50 ms to within 2% of nominal

 

 

Rated Output Current (rms)

15 A

 

25 A

 

33.3 A

 

41.6 A

Max Peak Output Current

45 A

 

75 A

 

100 A

 

125 A

Inverter Overload Capacity

 

 

125% for 30 sec./150% for 10 sec.

Bypass Overload Capacity

 

 

125% for 10 min./1000% for 1 cycle

Crest Factor

 

 

 

3.0

 

 

 

 

 

 

 

 

 

 

1.Input/output figures rated for 240 volts unless otherwise stated. Output ratings given for 0.85PF are only valid when the input voltage is greater than 204 volts; otherwise, ratings given for 0.70PF are applicable.

2.Battery backup time may vary depending on the operating conditions and ambient temperature at the installation site.

3.An initial charge time of 24 hrs. is necessary to obtain proper battery performance level before unit is placed in operation.

1600XP Series Installation and Operation Manual

A1

Page 67
Image 67
Toshiba operation manual Appendix a 1600XP Specifications, Standard Model 3.6 10 kva