14. Touchscreen Menu Tree

14.1 Front Panel Layout

The diagram below shows the menu tree for the touchscreen display. The four folder tabs and their associated sub-menu choices are shown on the left, and a description of the displays /choices are detailed on the right.

Tab: Main ID / RUN-STOP

Tab: Monitor Monitor Menu

IN

DC

OUT

BYP

Tab: Settings Settings Menu

ID

Output

DC Bus

Ctrl/Cfg

Disp/Reye

Tab: Records Records Menu

Test

Faults

Operation

BAT

C&C

D&R

Input

Bypass

Batt

History

Backup

Warnings

System

MAIN – Displays the starting screen. It has a RUN and STOP key that place the UPS in In-Line or Bypass mode respectively.

MONITOR – Graphically displays the current status of the UPS (On- Line, Backup, Bypass, Shutdown) in an interactive power flow block diagram. Selecting one of the blocks provides additional detailed data of the Input (IN), Output (OUT), Bypass (BYP), Battery (BAT), and DC Bus (DC), Control & Configura- tion (C&C), and Display & External (D&E) devices.

SETTINGS – Allows monitoring and/or modification of UPS pa- rameters. Parameters that can be viewed or modified vary depending on the security level of the login password entered using keypad.

Records – Displays the most re- cent 32 Test, Backup, Faults, Warning, Operation, and System change records.

System records are only available at the distributor and depot security levels.

In any record set, if more than 32 incidences have occurred, only the most recent 32 record are retained in each report.