22. UPS Protection System
22.1 System Protection Features
The following schematic shows the electrical locations of the protection devices on the UPS.
MCCB
Input | Line Filter | |
Power | ||
| ||
| Surge | |
| Absorber |
Input
Abnormal
Overheating | Overcurrent | Current Limit | ||
| ||||
|
|
| ||
|
|
| Overload | |
Bypass | *Static Switch |
| ||
| Isolation | |||
|
|
| ||
Input |
| Output | Transformer | |
Fuse |
| Fuse | Output | |
Rectifier/ | Inverter | |||
Chopper | Power | |||
| ||||
Batteries | + | * Switches are |
| |
|
| |||
| – |
| ||
| solid state | Power Flow | ||
Negative | devices. | |||
|
| Bus | Overvoltage/ |
Low Battery |
| |
| Undervoltage | |
Level |
| |
|
|
22.2 System Protection Functions
The following charts show the
Protection Item | Output Overvoltage |
| Output Undervoltage | Output Overload | |
LCD Message |
|
|
| OVERLOAD | |
|
|
|
|
| |
Cause | Control malfunction; |
| Control malfunction; | Overload – Short circuit at load | |
EEPROM error |
| Fuse opened; Load issue | |||
|
|
| |||
Operation Mode | Bypass operation – Chopper and inverter are | Inverter OL: Transfer to bypass; | |||
Bypass OL: Inverter, chopper | |||||
After Fault | stopped | ||||
stopped | |||||
|
|
|
| ||
Audible Alarm | Yes – Continuous buzzer | See Audible Alarm Functions on | |||
page 33 | |||||
|
|
|
| ||
Visible Alarm | Red Fault LED on | Inverter OL: Fault lamp off | |||
Bypass OL: Fault lamp on | |||||
|
|
|
| ||
Relay Contact | Fault relay closed | Fault relay open; | |||
Inverter OL: Bypass relay closed | |||||
Alarm | Bypass relay closed | ||||
Bypass OL: Bypass relay open | |||||
|
|
|
| ||
| No | Inverter OL: Yes if bypass is OK | |||
| Bypass OL: No | ||||
|
|
|
|
46 | 1600XP Series Installation and Operation Manual |