Toshiba 1600XP operation manual Capacity KVA 11.9 kW1 KVA 15.3 kW1 KVA 18.7 kW 1

Models: 1600XP

1 100
Download 100 pages 60.45 Kb
Page 72
Image 72

STANDARD MODELS: 14 – 22 KVA (CONT’D)

Capacity

14 kVA (11.9 kW)1

18 kVA (15.3 kW)1

22 kVA (18.7 kW) 1, 2

Mechanical Design

Enclosure

Enclosure of unit made from sheet metal meeting NEMA1 and UL

Size (HxWxD) (max)

39.0 x 17.5 x 36.1 in.

 

(991 x 445 x 917 mm)

 

 

 

 

 

 

 

Paint System

Powder coating

 

Fan Panel

Panel mounted on back of UPS to allow for

 

easy replacement of fans

 

 

 

Battery System

 

 

 

Battery Replacement

Slide out battery packs accessible from front of UPS,

factory or authorized service center serviceable only

 

Battery Packs

Designed for battery acid leakage containment with (6) batteries per pack

Battery Pack Size

5.0 x 7.3 x 19.0 in.

 

(HxWxD) max.

(127 x 185 x 462 mm)

 

 

 

 

 

Battery Pack Quantity

8

 

 

Battery Manufacturer

YUASA

 

Battery Type

REW45-12FR

 

Toshiba Part Number for

51896-FS

 

60995-FS

Battery Pack

 

 

 

 

1.Input/output figures rated for 240 volts unless otherwise stated. Output ratings given for 0.85PF are only valid when the input voltage is greater than 204 volts; otherwise, ratings given for 0.70PF are applicable.

2.Derate to 18.7 kVA (15.9 kW) for 50 Hz operation.