Toshiba 1600XP operation manual Chrgov

Models: 1600XP

1 100
Download 100 pages 60.45 Kb
Page 80
Image 80

B-8

1600XP Series Installation and Operation Manual

1600XP Command Parameters Table

Cmd

Description

Brief Description

Location Map

Example

Rqd Security

By

ID

on LCD

 

 

 

 

Level to change

 

 

Tab

Block

 

 

527

Ex Batt Rated

External battery’s Rated Ampere-Hour capacity

Settings

BATT

9 AHr

Nonchangeable

User

 

Ahr

 

 

 

 

Changeable

Administrator

 

 

 

 

 

 

Changeable

Service

 

 

 

 

 

 

 

 

528

Ex Batt C Rate

External Battery C rate

Settings

BATT

0 C

Nonchangeable

User

 

 

 

 

 

 

Changeable

Administrator

 

 

 

 

 

 

Changeable

Service

 

 

 

 

 

 

 

 

529

Ex Batt Ins

External Battery Installation Date

Settings

BATT

01/01/2008

Nonchangeable

User

 

Date

 

 

 

 

Changeable

Administrator

 

 

 

 

 

 

Changeable

Service

 

 

 

 

 

 

 

 

532

Vbat Gain

Battery Voltage Gain

Setting

BATT

8298

Changeable

Service

 

 

 

 

 

 

 

 

533

Vbat Offset

Battery Voltage Offset

Setting

BATT

0

Changeable

Service

 

 

 

 

 

 

 

 

544

Charger

Charger Reference (Normal Charging Mode)

Setting

BATT

55

Changeable

Service

 

Ref(Norm)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

545

Low Batt Level*

Low Battery Level in Percentage

Settings

BATT

90 %

Nonchangeable

User

 

 

- Percentage of nominal (# battery in series *

 

 

 

Nonchangeable

Administrator

 

 

12 Vdc) will issue low battery warning during

 

 

 

Changeable

Service

 

 

Backup

 

 

 

 

 

 

 

 

 

 

 

 

 

546

VChrgOV De-

Battery Overvoltage Fault Detection Delay

Settings

BATT

60 Sec

Nonchangeable

User

 

Delay

- Configurable between 0 to 300 Sec

 

 

 

Nonchangeable

Administrator

 

 

 

 

 

 

Changeable

Service

 

 

 

 

 

 

 

 

548

Charger

Charger Reference (Preventive Chargin Mode)

Settings

BATT

150

Changeable

Service

 

Ref(Prev)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

550

CHRGOV

Charger Overvoltage Detection Level

Settings

BATT

117

Changeable

Service

 

DeLevel

 

 

 

 

 

 

 

 

 

 

 

 

 

 

551

CHRGOV

Charger Overvoltage warning detection delay

Settings

BATT

8

Changeable

Service

 

WrnDeDelay

 

 

 

 

 

 

 

 

 

 

 

 

 

 

552

CHRGOV

Charger Overvoltage warning recovery delay

Settings

BATT

1

Changeable

Service

 

WrnReDelay

 

 

 

 

 

 

 

 

 

 

 

 

 

 

553

CHRGOV

Charger Overvoltage fault detection delay

Settings

BATT

1

Changeable

Service

 

FltDeDelay

 

 

 

 

 

 

 

 

 

 

 

 

 

 

554

En ChrgCtler

Enable Charger controller

Settings

BATT

1

Changeable

Service

 

 

 

 

 

 

 

 

555

Restart

Restart Charger controller

Settings

BATT

0

Changeable

Service

 

ChrgCler

 

 

 

 

 

 

 

 

 

 

 

 

 

 

556

Ibatt Multiplier

Battery Curretn Multiplier

Settings

BATT

12

Changeable

Service

 

 

 

 

 

 

 

 

Page 80