![](/images/new-backgrounds/1299066/299066159x1.webp)
1600XP Series Installation and Operation Manual
1600XP Command Parameters Table
Cmd | Description | Brief Description | Location Map | Example | Rqd Security | By | |
ID | on LCD |
|
|
|
| Level to change |
|
| Tab | Block |
|
| |||
527 | Ex Batt Rated | External battery’s Rated | Settings | BATT | 9 AHr | Nonchangeable | User |
| Ahr |
|
|
|
| Changeable | Administrator |
|
|
|
|
|
| Changeable | Service |
|
|
|
|
|
|
|
|
528 | Ex Batt C Rate | External Battery C rate | Settings | BATT | 0 C | Nonchangeable | User |
|
|
|
|
|
| Changeable | Administrator |
|
|
|
|
|
| Changeable | Service |
|
|
|
|
|
|
|
|
529 | Ex Batt Ins | External Battery Installation Date | Settings | BATT | 01/01/2008 | Nonchangeable | User |
| Date |
|
|
|
| Changeable | Administrator |
|
|
|
|
|
| Changeable | Service |
|
|
|
|
|
|
|
|
532 | Vbat Gain | Battery Voltage Gain | Setting | BATT | 8298 | Changeable | Service |
|
|
|
|
|
|
|
|
533 | Vbat Offset | Battery Voltage Offset | Setting | BATT | 0 | Changeable | Service |
|
|
|
|
|
|
|
|
544 | Charger | Charger Reference (Normal Charging Mode) | Setting | BATT | 55 | Changeable | Service |
| Ref(Norm) |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
545 | Low Batt Level* | Low Battery Level in Percentage | Settings | BATT | 90 % | Nonchangeable | User |
|
| - Percentage of nominal (# battery in series * |
|
|
| Nonchangeable | Administrator |
|
| 12 Vdc) will issue low battery warning during |
|
|
| Changeable | Service |
|
| Backup |
|
|
|
|
|
|
|
|
|
|
|
|
|
546 | VChrgOV De- | Battery Overvoltage Fault Detection Delay | Settings | BATT | 60 Sec | Nonchangeable | User |
| Delay | - Configurable between 0 to 300 Sec |
|
|
| Nonchangeable | Administrator |
|
|
|
|
|
| Changeable | Service |
|
|
|
|
|
|
|
|
548 | Charger | Charger Reference (Preventive Chargin Mode) | Settings | BATT | 150 | Changeable | Service |
| Ref(Prev) |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
550 | CHRGOV | Charger Overvoltage Detection Level | Settings | BATT | 117 | Changeable | Service |
| DeLevel |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
551 | CHRGOV | Charger Overvoltage warning detection delay | Settings | BATT | 8 | Changeable | Service |
| WrnDeDelay |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
552 | CHRGOV | Charger Overvoltage warning recovery delay | Settings | BATT | 1 | Changeable | Service |
| WrnReDelay |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
553 | CHRGOV | Charger Overvoltage fault detection delay | Settings | BATT | 1 | Changeable | Service |
| FltDeDelay |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
554 | En ChrgCtler | Enable Charger controller | Settings | BATT | 1 | Changeable | Service |
|
|
|
|
|
|
|
|
555 | Restart | Restart Charger controller | Settings | BATT | 0 | Changeable | Service |
| ChrgCler |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
556 | Ibatt Multiplier | Battery Curretn Multiplier | Settings | BATT | 12 | Changeable | Service |
|
|
|
|
|
|
|
|