2. Expanded Functions
2.1 System operation
2.1.1Auto-RUN / Standby selection
The initial operation mode (HALT or RUN) just after power on is determined by the
When the setting status is;
Standby: The T3H stays in HALT mode regardless of the mode control switch (HALT / RUN /
The
NOTE | (1) The default setting is Standby. |
|
(2)Different from the T3H, in case of the T3, this selection is made by the hardware switch (RAM/ROM switch).
2.1.2Timer interrupt interval
In the T3H, the timer interrupt program is available with the interval setting of 1 to 1000 ms in 1 ms increments.
(In case of the T3, it is 2 to 1000 ms in 1 ms increments)
NOTE | If you use the timer interrupt with 1 ms interval, consider to minimize the |
| |
| execution time of the timer interrupt program. If the interrupt task requires |
| long time, the T3H cannot assign enough time for main program execution. |
| As the result, scan time over error will occur. |
In case of the T3H, SFC (Sequential Function Chart) can also be programmed on the interrupt program, as well as Ladder diagram.