66 PROSEC T3H
2. Expanded Functions

2.4.6 Network data receive (RECV)

FUN 240 RECV Network data receive

Expression

Input [ A RECV B ] Output

Function

This instruction reads the designated range of register data from another T3H through the network.
(Network: TOSLINE-S20LP or Ethernet)
The transfer source register (target-station) is designated by A+5 and A+6.
The transfer destination register (self-station) is designated by A+3 and A+4.
The transfer size (number of words) is designated by A+2. The maximum transfer size is 128 words (S20LP),
or 485 words (Ethernet).
The designation method of the target-station is different between S20LP and Ethernet.
This instruction is also used for other functions of the Ethernet module. Refer to the Ethernet module (EN311)
manual for detailed functions used for the EN311.

Execution condition

Input Operation Output ERF
OFF No execution OFF
ON During execution OFF
Normal complete ON
When error is occurred (see Note) ON Set

Operand

Name Device Register Con- Index
X Y S L R Z T. C. I O X
W Y
W S
W L
W R
W W T C D F I
W O
W I J K
stant
A Transfer
parameter
B Status
< In case of S20LP > < In case of Ethernet >
F C B 8 7 0 F C B 8 7 0
A MID CH Target station No. A MID CH 0 (fixed)
A+1 0 (fixed) A+1 Request command
A+2 Transfer size A+2 Transfer size
A+3 Register type (self-station) A+3 Register type (self-station)
A+4 Leading address (self-station) A+4 Leading address (s elf-station)
A+5 Register type (target-station) A+5 Register type (target-station)
A+6 Leading addres s (target-station) A+6 Leading address (target-station)
A+7 Response time limit A+7 Response time limit
A+8 Target-station IP address
A+9
A+10 Target-station UDP port No.
Note) Parameters for the Ethernet varies depending on the request com mand. Above figure shows the
parameters for the register read/write command (H0021). Refer to the EN311 manual.