50 PROSEC T3H
2. Expanded Functions

Manual mode
In this mode, the manipulation value MV can be directly controlled by the input value of MMV.
MV differential limit for manual mode DMMV is effective. MH/ML and DMV are not effective.
When mode is changed from manual to auto or cascade, the operation is started from the current MV.
Cascade mode
This is a mode for PID cascade connection. PID is executed with CSV as set value.
Different from the auto mode, set value differential limit is not effective. Manipulation value upper/lower
limit MH/ML and differential limit DMV are effective.
Bump-less changing from cascade mode to manual mode is available. (Manual mode m anipulation
value MMV is over-written by current MV automatically. MMV MV)
And, bump-less changing from cascade mode to auto mode is available. (Auto mode set value ASV is
over-written by current CSV automatically. ASV CSV)
MV tracking
This function is available in auto and cascade modes. When the tracking designation (A+5 bit 2) is ON,
tracking input TMV is directly output as MV.
Manipulation value upper/lower limit MH/ML is effective, but differential limit DMV is not effective.
When the tracking designation is changed to OFF, the operation is started from the current MV.

Note

PID3 instruction is only usable on the main-program.
PID3 instruction must be used under the constant scan mode. The constant scan interval can be selected
in the range of 10 to 200 ms, 10 ms increments.
The data handled by the PID3 instruction are % units. Therefore, process input value PVC, manipulation
value MV, etc., should be converted to % units (scaling), before and/or after the PID3 instruction. For this
purpose, the function generator instruction (FUN165 FG) is convenient.