2. Expanded Functions
When “GLOBAL” setting is used, the link registers of “GLOBAL” setting block are assigned to both CH1 and CH2 S20’s.
T3H’s link register | Block | Setting | CH1 S20 | CH2 S20 | |
W |
| CH1 | CH2 | scan memory | scan memory |
|
|
|
|
|
|
W0192 - W0255 | 4 | LINK |
| 0192 - 0255 | - |
W0256 - W0319 | 5 | GLOBAL |
| 0256 - 0319 | 0256 - 0319 |
W0320 - W0383 | 6 | GLOBAL |
| 0320 - 0383 | 0320 - 0383 |
W0384 - W0447 | 7 | GLOBAL |
| 0384 - 0447 | 0384 - 0447 |
W0448 - W0511 | 8 | GLOBAL |
| 0448 - 0511 | 0448 - 0511 |
W0512 - W0575 | 9 | LINK |
| 0512 - 0575 | - |
|
|
|
|
|
|
W1216 - W1279 | 20 |
| LINK |
| 0192 - 0255 |
W1280 - W1343 | 21 |
|
| - | - |
W1344 - W1407 | 22 |
|
| ||
W1408 - W1471 | 23 |
|
|
|
|
W1472 - W1535 | 24 |
|
|
|
|
W1536 - W1599 | 25 |
| LINK |
| 0512 - 0575 |
|
|
|
|
|
|
•The blocks 1 - 16 are dedicated to the CH1 S20, and the blocks 17 - 32 are dedicated to the CH2 S20.
It is not allowed to assign the blocks 1 - 16 to CH2, and blocks 17 - 32 to CH1.
•For the blocks set as “LINK” or “GLOBAL”, the T3H performs data read from S20 (for data receive area) and data write to S20 (for data send area).
The data transfer direction (read or write) is automatically decided by the T3H according to the S20’s receive/send setting.
•For the blocks set as “GLOBAL”, the data transfer is as follows.
1)If CH1 is receive and CH2 is send;
CH1 receive data is read and written into both W register and CH2.
2)If CH1 is send and CH2 is receive;
CH2 receive data is read and written into both W register and CH1.
3)If both CH1 and CH2 are send;
W register data is written into both CH1 and CH2.
4)If both CH1 and CH2 are receive;
The receive data of “GLOBAL” setting channel is read and stored in W register.
NOTE
In case of
User’s Manual 33