2. Expanded Functions

B+17B+16

Initial status STS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

B+17

 

 

 

 

 

B+16

 

 

 

 

 

 

 

 

 

 

F

0 F

 

 

C

8

 

 

4

0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Initial operation mode

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

00

: Manual mode

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

01

: Auto mode

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10

: Cascade mode

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

11

: (Reserve)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Direct / reverse selection

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0 : Direct

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1 : Reverse

B+19B+18

MV upper limit MH (-25 to 125 %)

 

 

 

 

 

 

Data range: -25.0 to 125.0

B+21B+20

MV lower limit ML (-25 to 125 %)

 

 

 

 

 

 

Data range: -25.0 to 125.0

B+23B+22

MV differential limit DMV (0 to 100 %/t)

 

 

 

 

 

 

Data range:

0.0 to 100.0

B+25B+24

Control interval setting n (1 to 32767 times)

 

 

 

 

Data range:

1.0 to 32767.0

 

 

Executes PID every n scan. Therefore, control interval t = n

constant scan interval

 

 

(It is treated as n = 1 when n

0)

 

 

 

 

 

 

 

 

 

 

 

 

 

C+1C

Manipulation value MV (-25 to 125 %)

 

 

 

 

 

 

Data range: -25.0 to 125.0

C+3C+2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

:Internal work area

C+15C+14

Operation

1. When the instruction input is OFF:

 

 

Initializes the FPID3 instruction.

 

 

Operation mode is set as specified by B+17B+16.

A+10 bit 0, 1 B+16 bit 0, 1

Auto mode SV is set as specified by B+9B+8.

ASV

ISV

Manual mode MV is set as current MV.

MMV

MV

Internal calculation data is initialized.

 

 

MV remains unchanged.

 

 

2.When the instruction input is ON:

Executes PID calculation every n scan which is specified by B+25B+24. The following operation modes are available according to the setting of A+11A+10.

Auto mode

This is a normal PID control mode with ASV as set value.

Set value differential limit DSV, manipulation value upper/lower limit MH/ML and differential limit DMV are effective.

Bump-less changing from auto mode to manual mode is available. (Manual mode manipulation value

MMV is over-written by current MV automatically. MMV MV)

54 PROSEC T3H

Page 56
Image 56