2. Expanded Functions

2.2.3 Timer

The T3H has 1000 points of timer.

Function type

Type

Address range

Quantity

Expression

 

code

 

 

example

Timer register

T

000 - 999

1000 words

T670

Timer device

T.

000 - 999

1000 points

T.670

The proportion of the 0.01 s base and the 0.1 s base timers within this 1000 points can be specified by user. This setting information is stored in the system information.

10 ms Timer Range Setting:

 

T000 - T [

]

User setting (max. 999)

NOTE

 

 

 

 

 

T3H internally, the register ranges T000 to T511 and T512 to T999 are

handled separately. Therefore, index modification or table designation

across these ranges are not allowed.

 

For example)

 

 

 

├─[ T450 TMOV

(100) D1000 ]-

Not allowed

├─[ T450

 

 

 

 

 

TMOV

(62)

D1000 ]-

Allowed

TMOV

(38)

D1062 ]-

 

├─[ T512

 

2.2.4 Link register

The T3H has 2048 words of link register. This link register is prepared for the TOSLINE-S20 (here called S20).

Function type

Type

Address range

Quantity

Expression

 

code

 

 

example

Link register

W

0000 - 2047

2048 words

W1500

Link device

Z

0000 - 999F

16000 points

Z847E

The link device Z corresponds to a bit in a link register W. The bit access as Z device is available for the leading 1000 words of W register.

User’s Manual 31

Page 33
Image 33
Toshiba PROSEC T3H user manual Timer, Link register