2. Expanded Functions

2.3 Network support function

2.3.1IC memory card data access through computer link

The expanded file register data stored in the IC memory card can be read/written through RS-485 computer link.

There are two types of data storage format for the IC memory card. They are 8 k words per bank and 64 k words per bank. (Refer to XFER instruction)

Note that the computer link command for these formats are slightly different.

Expanded file register data read [MR]

Request message format (Host

 

T3H):

 

 

 

 

 

 

 

 

 

 

 

 

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

19

20

21

22

23

(

A

ADR

M R

Starting register

, Bank ,

N

& Sum )

CR

Can be shortened

Can be omitted

ADR: Station address ... 01 to 32

Starting register:

For 8 k words per bank ..... F0000 to F8191

For 64 k words per bank ... f0000 to f65535 (bank 1) f0000 to f57343 (bank 2)

Bank: For 8 k words per bank ..... 1 to 15

For 64 k words per bank ... 1 to 2

Upper case F

Lower case f

N:Number of registers to be read ... 1 to 61 (61 words max.)

Sum: Check sum

Response message format (T3H

Host):

 

 

 

 

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

( A

ADR M R

Data #1

Data #2

n-5 n-4 n-3 n-2 n-1 n

Data #N-1

Data #N

& Sum )

CR

Data: Data in hexadecimal

38 PROSEC T3H

Page 40
Image 40
Toshiba PROSEC T3H user manual Expanded file register data read MR, Starting register