2. Expanded Functions

Inside the parameter (cont’d):

Status

S20LP

Ethernet

Abn

0: Normal complete

 

 

1: Error complete

 

Busy

0: Initial state

 

 

1: Transmission port busy

 

Status

0: Initial state

 

 

1: While send requesting

 

 

2: While waiting response

 

 

3: Complete

 

TermSTS

H00: Normal complete

 

 

H01: Register designation error

 

 

H02: Response time-out

 

 

H03: Parameter error

 

 

H04: Register write protect

 

 

H05: (Reserve)

 

 

H06: Module error (send time-out)

 

 

H07: No send channel

 

 

H08: Invalid station No.

 

 

H09: Transfer size error

 

 

H0A: Boundary error

 

 

H0B: Transmission error

Bit 7 indicates the error is occurred

 

H0C: I/O no answer error

whether self-station or target-station.

 

H0D: IC card designation error

0: Self-station

 

H0E: (Reserve)

1: Target-station

 

H0F: (Reserve)

 

Transmission error

When TermSTS is H0B, the error information is stored. (0 for other cases)

information

For detailed information, refer to the S20LP or EN311 manual.

Example

RW030

3

 

1

 

0

RW031

 

 

 

33

(H21)

RW032

 

 

 

 

 

200

RW033

 

 

 

 

 

5

RW034

 

 

 

 

 

5000

RW035

 

 

 

 

 

4

RW036

 

 

 

 

 

4000

RW037

 

 

 

 

 

50

RW038

 

 

H71

 

 

H85

RW039

 

 

H0A

 

 

H62

RW040

 

 

 

 

 

1024

RW060

 

 

 

 

 

 

0

0

1

 

0

 

0

RW061

 

 

 

 

 

0

Ethernet, channel 1

Request command H21: Register read/write

Transfer size: 200 words Self-station F register Leading address: F5000 Target-station D register Leading address: D4000 Response time limit: 5 second Target-station IP address:

133.113.98.10 = H85.H71.H62.H0A Target-station UDP port No.: 1024

Send requesting

68 PROSEC T3H

Page 70
Image 70
Toshiba PROSEC T3H user manual S20LP, H0A