Toshiba RAV-SM1404BT-E, RAV-SM454MUT-E, RAV-SM404MUT-TR 30, Item, Remarks, Ceiling type

Models: RAV-SM454MUT-TR RAV-SM564CT-E RAV-SM564BT-E RAV-SM564MUT-E RAV-SM564BT-TR RAV-SM564MUT-TR RAV-SM804BT-TR RAV-SM804BT-E RAV-SM1104BT-TR RAV-SM1404BT-TR RAV-SM1104BT-E RAV-SM1404BT-E RAV-SM404MUT-TR RAV-SM454MUT-E

1 120
Download 120 pages 15 Kb
Page 30
Image 30
(Ceiling type)

No.

Item

 

 

Outline of specifications

 

 

 

Remarks

 

 

 

 

 

 

 

 

 

 

 

 

 

6

Fan speed control

(Ceiling type)

 

 

 

 

 

 

 

 

 

 

 

(Continued)

 

 

 

 

 

 

 

 

 

 

 

Selection of high

 

 

CODE No.

Standard

Type 1

Type 3

Type 6

 

 

 

ceiling type

 

 

 

[5d]

0000

0001

0002

0003

 

 

 

CODE No.: 5d

 

 

 

SW501 (1)/(2)

OFF/OFF

ON/OFF

OFF/ON

ON/ON

 

 

 

Tap

HEAT

COOL

HEAT

COOL

HEAT

 

COOL

HEAT

COOL

 

 

 

 

F1

 

 

 

 

HH

 

HH

HH

HH

 

 

 

 

F2

 

 

HH

HH

 

 

 

 

 

 

 

 

 

F3

 

 

 

H+

H+, H

 

H+, H

H+, H

H+, H

 

 

 

 

 

 

 

 

 

 

 

 

L+, L

L+, L

 

 

 

 

F4

 

 

H+

 

 

 

 

 

 

 

 

 

 

F5

 

HH

 

H

 

 

 

 

 

 

 

 

 

F6

HH

 

H

 

L+

 

L+

 

 

 

 

 

 

F7

H+

H+

 

 

L

 

L

 

 

 

 

 

 

F8

 

H

 

L+

 

 

 

 

 

 

 

 

 

F9

H

 

L+

L

 

 

 

 

 

 

 

 

 

FA

 

L+

L

 

 

 

 

 

 

 

 

 

 

FB

L+

L

 

 

 

 

 

 

 

 

 

 

 

FC

L

 

 

 

 

 

 

 

 

 

 

 

 

FD

 

UL

 

UL

 

 

UL

 

UL

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3)In heating operation, the mode changes to [UL] if thermostat is turned off.

4)If Ta 25°C when heating operation has started and when defrost operation has been cleared, the air conditioner

 

operates with (H) mode or higher mode for

However only when

 

1 minute after Tc entered in E zone of cool air discharge

 

the high ceiling

 

preventive control (No. 7).

 

 

 

selection is set to

5)

In automatic cooling/heating operation, the revolution

[Standard]

 

frequency of (HH) is set larger than that in the standard

 

 

cooling/heating operation.

 

 

Ta ˚C

F5 F4

 

 

 

 

 

 

47

 

However the revolution frequency

 

 

 

 

 

 

 

 

is restricted in the automatic

 

 

42

 

heating operation as shown in

 

 

 

the following figure.

 

 

 

F5

 

 

6)

Self-clean operation

 

[Self-clean ] is

 

When performing self-clean operation after stopping the

displayed.

 

cooling operation, the mode becomes 210 rpm.

 

7

Cool air discharge

1)

In heating operation, the indoor fan is controlled based on

In D and E zones,

 

preventive control

 

the detected temperature of Tc sensor or Tcj sensor. As

the priority is given

 

 

 

shown below, the upper limit of the revolution frequency is

to air volume

 

 

 

restricted.

 

 

selection setup of

 

 

 

However B zone is assumed as C zone for

remote controller.

 

 

 

6 minutes and after when the compressor activated.

In A zone while

 

 

 

In defrost operation, the control value of Tc is shifted by 6°C.

thermo is ON,

 

 

 

Tc, Tcj

 

 

[PRE-HEAT

 

 

 

 

 

(Heating ready)] is

 

 

 

˚C

HH

 

displayed.

 

 

 

32

 

 

 

 

H

 

 

 

 

 

30

 

 

 

 

 

L

E zone

 

 

 

 

 

 

 

 

 

28

 

 

 

 

 

UL

D zone

 

 

 

 

 

 

 

 

 

26

 

 

 

 

 

 

 

 

 

 

 

20

OFF

C zone

 

 

 

 

 

B zone

 

 

 

 

16

 

 

 

 

 

 

A zone

 

 

 

 

 

 

 

– 30 –