No.

Item

 

Outline of specifications

Remarks

 

 

 

 

 

21

8°C heating/Frost

1)

This functional is intended for the cold latitudes and

 

 

protective operation

 

performs objective heating operation

 

 

 

 

(8°C heating operation).

In a group connection,

 

 

2)

This function is valid only for combination with the

if there is even one

 

 

 

outdoor units.

combination with other

 

 

3)

Using the indoor CODE No. [D1] (1 bit), Valid/Invalid of

unit, “This function is not

 

 

provided.” is displayed.

 

 

 

this function is set up at the customer’s side.

 

 

 

 

The setup by CODE No. is Invalid [0]/Valid [1] and Invalid [0] has been set at the shipment.

4)This operation is the heating operation which sets 8°C

as the setup temperature of the target.

The setup temperature

5) This function starts operation by pushing temperature

jumps from [18] to [8].

button

during heating operation; besides by

 

pushing

button for 4 seconds or more after

 

temperature reached the minimum set temperature.

 

6)To stop/release this operation, select and execute one from the following operations.

Q Push button:

Heating operation 18°C setting) continues.

R Push [START/STOP] button: Air conditioner stops.

(Heating 18°C operation at the next start)

S Push MODE :

Other operation mode is selected and the operation continues.

7)As the setup temperature is 8°C and the human heating is not targeted, the cold air discharge preventive control (Item 7) is made invalid to suppress the intermittent operation.

8)The settings of the air direction and air volume are changeable during this operation.

9)The indoor fan stops to protect the compressor for 2 minutes after start of heating operation (Thermo-ON) by this function.

– 39 –